Tab. 10: 1500 ... 3500 g/h
Capacity
g/h
1500
1750
2000
2500
3000
3500
kg/24 h 33
38.5
48
60
72
84
Dimensions
mm
1650x600x2000
1750x1200x2000
Space requirement
mm
2250x1500
2350x2400
Transport weight
kg
650
1150
Brine tank
Litres
380
520
Recommended product tank
Litres
1700
2000
2200
3000
3300
4000
Process data
Number of cell chambers
-
5
5
6
8
10
10
Water needed*
l/h
240
250
280
350
420
490
Process water
l/h
60
70
80
100
120
140
Cooling water 20 °C**
l/h
180
180
200
250
300
350
Salt
kg/day
70
80
100
125
150
175
Dilution air***
m
3
/h
119
138
158
198
237
277
Product concentration
20 ... 25 g/l
Ambient temperature
10 ... 35 °C
Maximum ambient air humidity****
85 %
Connectors
Raw water feed
20 mm
Brine for softener
20 mm
Brine for membrane cell
20 mm
Filling the brine tank
20 mm
Product outlet
20 mm
Bleeding, diluted hydrogen*****
110 mm
125 mm
Waste water duct
50 mm
Cooling, output
20 mm
Remarks
*
Maximum water hardness = 15 °dH, minimum pressure 2.5 bar
**
Depending on the actual water temperature, maximum 20 °C
***
Ensure minimum dilution to 0.4 % of the lower explosion limit with a fan
****
Non-condensing, non-corrosive and dust-free ambient air in the installation room
*****
Maximum 10 metres of pipe with a maximum of 3 bends
Technical data
112
Summary of Contents for Chlorinsitu-III
Page 18: ...A1706 15 4 13 3 3 16 12 17 Fig 8 Components of the system side B Components of the system 18 ...
Page 117: ...117 ...