Step
OK
24
Switch on production in the display.
25
Check whether the booster pump is running and the caustic tank stops filling.
26
Check that all parts fitted by the customer are working correctly.
27
Check the cooling fans for the membrane cells and the control cabinet.
28
Manually start "Refill anode".
After 2 hours of production:
29
Measure the voltage at the membrane cells and check whether it corresponds to the specifica‐
tion in the list of basic settings.
30
Measure the mains current at full production.
31
Check the modem or internet connection, if available.
32
Take a sample of the product.
33
Measure the free chlorine and pH value of the sample from the production tank.
34
If the free chlorine is approx. 25 g/l, then sign the handover report.
35
Photograph the system.
8.3 Commissioning work
n
User qualification, commissioning: Service
Ventilate the room.
Wear safety gloves.
Wear safety glasses.
Caution high voltage.
Danger due to corrosive dust.
Commissioning
40