11.10.1 Renewing the chlorine gas sensor
A2009
2.
1.
3.
4.
Fig. 87: Renewing the chlorine gas sensor
1.
Remove the sensor from its holder (1).
2.
Remove the protective cap (2) from the new chlorine gas
sensor.
3.
Observe the instructions for the chlorine gas detector.
Enter the resistance value (4) of the new chlorine gas sensor
in
[nA/ppm] into the chlorine gas detector.
4.
Using the positioning system (3), fit the new chlorine gas
sensor into the correct position in the holder.
11.10.2 Testing the Chlorine Gas Sensor
A2010
1.
2.
Fig. 88: Testing the chlorine gas sensor
1.
Hold a measuring cup (2) containing a small amount of
chlorine product under the chlorine gas sensor (1).
2.
Check whether the alarm is triggered when chlorine gas is
detected and the Chlorinsitu
®
-III system switches to fault
mode.
ð
Should no fault occur, then read the "Troubleshooting"
section of the chlorine gas detector instruction manual.
3.
Eliminate the fault and start up production.
During annual maintenance:
Preventative maintenance
106