Faults first have to be eliminated if the system is
not producing due to faults or if the control points
are not met. Refer to the "Troubleshooting" section
for information on eliminating faults.
Apart from normal tools, a number of special tools and equipment
are needed to perform maintenance work:
n
Multimeter
n
DC current clamp
n
Bucket, 20 litres (dry and without residue)
n
Measuring cup, 5 litres
n
Chlorinsitu
®
-III > 500 g/h approx. 5 litres 33 % sodium
hydroxide solution.
10.2.2 Maintenance kits
The manufacturer of the system has a "1-year" maintenance kit
and a "3-year" maintenance kit. Use the following order numbers to
order these maintenance kits.
Tab. 4: Maintenance kits
Maintenance kit
Order number
Maintenance kit 3, 100 ... 500 g/h
1097459
Maintenance kit 1, 100 ... 500 g/h
1097456
Maintenance kit 3, 600 ... 1750 g/h
1097460
Maintenance kit 1, 600 ... 1750 g/h
1097457
Maintenance kit 3, 2000 ... 3500 g/h
1097461
Maintenance kit 1, 2000 ... 3500 g/h
1097458
10.2.3 Maintenance Schedule
Daily:
n
Check whether there is sufficient salt in the brine storage tank.
The brine storage tank should have a minimum of 70 cm of
salt.
n
Check that the vacuum system is operating correctly.
n
Manually check the hardness of the softened water.
Use the test kit provided.
n
Check the system for leaks.
Once a week:
n
Check that the water softener is operating correctly.
Use the test kit to determine the hardness of the softened water.
Proceed as follows:
Material:
n
Volumetric flask with 100 ml markings
n
Reagent 1, buffer solution,
[HARDNESS 1]
Maintenance kits
Water hardness testing process
Maintenance checks and preparation for maintenance
57
Summary of Contents for Chlorinsitu-III
Page 18: ...A1706 15 4 13 3 3 16 12 17 Fig 8 Components of the system side B Components of the system 18 ...
Page 117: ...117 ...
Page 118: ...118 ...
Page 119: ...119 ...