11.6.1 Preparation for Maintenance on the Membrane Cell
WARNING!
Danger from chemical residue
Possible consequence: Fatal or very serious inju‐
ries from chemical residue
Measure: During maintenance wear the goggles
and gloves provided.
Ventilate the room during maintenance.
Chlorinsitu
®
-III 100 ... 500 g/h membrane cell
This example showed a Chlorinsitu
®
-III 100 ... 500
g/h membrane cell. The same provisions apply to
the Chlorinsitu
®
-III 600 ... 3500 g/h.
11.6.2 Replacing the O-rings on the Anode Side of the Membrane Cell
A1993
1.
2.
3.
Fig. 73: O-rings on the anode side
1.
Close the refresh tap (1)
2.
Close the brine tap (2)
3.
Tighten the threaded connector on the membrane cell.
4.
Manually open the bleed valve (3).
5.
Replace the O-rings on the anode side of the membrane cell
Preventative maintenance
95