4. Details of Parameter
[Class 4] I/F Monitor Setting
Pr4.42
2nd Positioning complete
(In-position) range
Range
Unit
Attribute
Default
Related
control code
0 to 2097152
Command
unit
A
8400
P
Caution
Note
The INP2 turns ON whenever the positional deviation is lower than the value set up in this
parameter, without being affected by Pr4.32 Positioning complete output setup. (Presence/
absence of positional command is not related to this judgment.)
The command unit is used as the default unit but can be replaced by the encoder unit by
using Pr5.20. Positioning unit selection. Note that when the encoder unit is used, unit of
Pr0.14 Positional deviation excess setup is also changed.
For description of “command unit” and “encoder unit”, refer to P.3-85 “Pr5.20”.
Pr4.44
Position comparison output
pulse width setting
Range
Unit
Attribute
Default
Related
control code
0 to 32767
0.1 ms
R
0
P S T
Sets the signal width of position comparison output.
No signal will be output when 0.
Pr4.45
Position comparison output
polarity selection
Range
Unit
Attribute
Default
Related
control code
0 to 7
—
R
0
P S T
Sets position comparison output polarity by each bit of the output terminal.
・
Set bits
*1 *2
bit
Designation
bit0
SO1,OCMP1
bit1
SO2,OCMP2
bit2
SO3,OCMP3
・
Set value for each bit
Setup value
Designation
0
The output photocoupler is turned ON for SO1 to 3 and is set to L level for
OCMP1 to 3, respectively, during pulse output.
1
The output photocoupler is turned OFF for SO1 to 3 and is set to H level for
OCMP1 to 3, respectively, during pulse output.
Basically, use this function as 0.
Pr4.47
Pulse output select
Range
Unit
Attribute
Default
Related
control code
0 to 1
—
R
0
P S T
Selects signal outputted from pulse regeneration output / position comparison output
terminal.
*2
0
:
Encoder output Signal (OA,OB) 1
:
Position comparison output signal (OCMP1 to 3)
*1 When general output (SO1 to SO3) is used as position comparision output(CMP-OUT),assign position
comparision to Pr4.10 to Pr4.12 for all control modes.
*2 When encoder output signal(OA,OB) is used as position comparision output(OCMP1 to 3),set Pr4.47 to 1.