Panasonic Electric Works Nordic AB
MEW01351
Rev: -
Planning Instructions Fire alarm system EBL512 G3, V1.1.x
134
Enhanced disablements
: Disabled alarm point
121
will not
activate pre-warning, fire alarm or fault.
Checkbox not marked = Disabled alarm point
121
will not activate
pre-warning or fire alarm. Fault can still be activated.
This is a violation to the EN54-2 standard.
20.1.4.1
Door closing by time
Active
: If all fire doors (trigger condition "Fire Door Closing")
shall be closed at a definite time every day, this checkbox shall be
marked and the time (
hh:mm
) set, e.g. 23:00.
20.1.4.2
Main power loss fault delay time (minutes)
A fault will be activated
mm
minutes after loss of mains (230 V AC).
0 is default. 0-300 minutes is possible.
20.2
Menu System
20.2.1
Properties
The same dialog box opens as in Figure 26, page 131.
20.2.2
Time channels
Always off and Always on cannot be edited.
The control unit RTC (real time clock) controls the time channels 2-
14.
Five intervals
(interval = one time on & one time off) can be set
for each day in time channel 2-14.
Time channels can:
disable and re-enable alarm points / zones
set Alert Annunciation on / off
121
The sensor values for a disabled analog smoke detector will not be saved.