Planning Instructions Fire alarm system EBL512 G3, V1.1.x
24
5.3
Programmable voltage outputs (S0-S3)
The 24 V DC outputs S0-S3 are supervised (monitored)
5
.
Connections according to dwg 512 G3 – 23. When all connections are
done a calibration has to be performed, see chapter "Calibration of
supervised outputs", page 110 and the EBL512 G3 Operating
Instructions MEW01163, chapter "Calibration of supervised outputs
(menu H5/A1)".
Each output has to be programmed (via WinG3) regarding:
Type of output, i.e. output for Control, Alarm devices, etc.
Logic, i.e. normally low (default)
or
normally high (24 V DC)
6
.
Activation time and type (steady, pulse, delay, etc.).
Control expression (one or more trigger conditions).
See also the WinG3 help and chapter "Programmable outputs", page
68.
5.4
Programmable relay outputs (R0-R1)
Connections according to dwg 512 G3 – 23.
Each output has to be programmed (via WinG3) regarding:
Type of output, i.e. output for Control, Alarm devices, etc.
Logic, i.e. normally open (NO)
or
normally closed (NC) contacts.
Activation time and type (steady, pulse, delay, etc.).
Control expression (one or more trigger conditions).
See also the WinG3 help and chapter "Programmable outputs", page
68.
5.5
Programmable inputs (I0-I3)
Connections according to dwg 512 G3 – 23.
Each input has to be programmed (via WinG3) regarding:
Trigger condition (Triggered by).
Logic, i.e. normally open (NO)
or
normally closed (NC) contacts.
Additional information, depending on the selected trigger
condition (Fault no., Zone, Address, Fault message (Error text),
etc.)
Open = R > 2K. Closed 0 R < 2K.
An input has to be activated > 0.5 sec.
See also the WinG3 help and chapter "Programmable inputs", page
62.
5
The outputs are in WinG3 default set as supervised but via WinG3 it is
possible to set each output (S0-S3) individually to be not supervised.
6
A normally high output is not supervised.