Panasonic Electric Works Nordic AB
MEW01351
Rev: -
Planning Instructions Fire alarm system EBL512 G3, V1.1.x
80
"Control, neutral".
78
See also chapter "Fire Door
Closing", page 88.
38
Service signal is activated (by any sensor).
79
39
This control expression is true when the control unit
standard output "Fire brigade tx" is activated.
NOTE!
Normally used with output type
Routing equipment (Fire
brigade tx)
.
40
Door open in the specific control unit.
75
41
This control expression is true when all control outputs of
the types
Control
,
Fire ventilation
and
Extinguishing
in
the specified control unit are disabled via menu H2/B7.
76
This output shall be type Control – neutral.
42
This control expression is true when all control outputs of
type
Alarm device
in the specified control unit are
disabled via menu H2/B8). This output shall be type
Control – neutral.
43
Any "Quiet alarm" in the specified zone. Used e.g. for
the fan control function.
44
One specified "Quiet alarm" in the specified zone. Used
e.g. for the fan control function.
45
Output
activated
when
input
trigger
condition
"Extinguishing system fault" is true.
46
Output
activated
when
input
trigger
condition
"Extinguishing system released" is true.
47
Output activated when input trigger condition "Activated
key cabinet" is true.
13.5.2
Logical operators
The logical operators available in WinG3 are in priority order:
( )
parentheses
, changes priority order
NOT
not
-function (inverts), is written NOT in WinG3
AND
and
-function, is written AND in WinG3
OR
or
-function, is written OR in WinG3
13.5.3
Control expression examples
In order to understand the possibilities to create control expressions,
here follow some AND, OR, NOT and ( ) examples and also some
control expression examples.
13.5.3.1
AND
a
AND
b
AND
c=y
78
In Danish convention (DBI), must only the c.i.e. outputs R0-R1 and S0-S3
be used (i.e. no COM loop units.) and the type has to be "control neutral".
79
Indicated by a "Service" symbol in the display symbol area.