Panasonic Electric Works Nordic AB
MEW01351
Rev: -
Planning Instructions Fire alarm system EBL512 G3, V1.1.x
46
3390
Label holder. To be mounted in an analog base (3312 / 3312F /
3312FL / 4313)
32
. Intended for a label with "zone-address",
"technical address", etc. to be read also when the detector is
plugged in its base. 100 label holders per packet. Excl. labels.
3391
Labels for 3390. A packet with self-adhesive white labels for
label holder 3390. 10 A4-sheets à 132 labels for laser printer
usage. The print-out is done via WinG3.
9.1.2
Addressable I/O units
3361
Addressable multipurpose I/O unit.
33
Power supplied via the
COM loop. The unit has two
programmable
inputs:
Monitored input
….used as zone line input (Z)
(terminals 6 & 7): End-of-line
capacitor 470 nF mounted in the last unit on the zone line.
Short circuit on the line can generate a fault or a fire alarm (set
via WinG3). This input is intended for conventional detectors.
34
Max. 1.5 mA. Cable: Max. 50 ohms and max. 5 nF.
....used as general input (In0)
(terminals 5 & 7): An input for
NC or NO contacts (set via WinG3).
Isolated input (In1)
(terminals 8 & 9): An optocoupler input
(external 24 V DC / 8 mA is required). Normally low or high
(set via WinG3).
The unit has two
programmable
relay
35
outputs:
Relay output (Re0)
: NC or NO contacts (set via WinG3).
Relay output (Re1)
: Like Re0.
Connections and examples, see drawings 512G3 - 31 & - 36.
Unit dimensions: (L x W x H) 90 x 70 x 32 mm.
A plastic protection cover is attached. The cover dimensions:
(L x W x H) 129 x 73 x 45 mm.
3361 is intended to be surface mounted and for indoor use in
dry premises. When required, the unit can be mounted in a
Waterproof (IP66 / 67) box (3362). 3361 has an LED to
indicate communication "OK" or alarm condition. For more
information, see the Product Leaflet. The COM loop address is
set with the Address setting tool (3314). The unit has an
32
Also in an enclosed analog heat detector (3309).
33
The same physical unit (3361) is also used for Fan control together with
the Fan control panel 4593. Then it has a separate dialog box in WinG3.
34
It is via WinG3 possible to define this input to function like a manual call
point ("Used as MCP"), i.e. it will
not
be collectively disabled via menu
"Disable zone, H2/B1", can
not
be included in two-unit dependence, it can
not
use the "alarm delay" function and it can
not
be disabled via a time
channel.
35
Relay contacts: max. 2 A @ 30 V DC / 125 V AC.