Planning Instructions Fire alarm system EBL512 G3, V1.1.x
43
0
10
20
30
40
50
60
70
0 4 8 12 16 20 24 28 32 36 40 44 48 52 56 60
Smoke value
T
e
m
p
e
r
a
tu
r
e
Figure 8. When the calculated value in the decision algorithm
exceeds the lower graph, pre-warning will be activated. When it
exceeds the upper graph, fire alarm will be activated.
Temperature
= °C
.
Smoke value
= obscuration (%/m) x 10
.
The Analog multi detector's COM loop address (Technical
address) is set with the Address setting tool (3314). The
detector has an address label on which the programmed
technical address can be written.
NOTE!
The multi detector in system EBL512 G3 takes
two
COM loop
(technical) addresses, one address that is set with the 3314 tool
but also the following address that will be "occupied" for the
heat part of the detector and cannot be used by any other unit
on the COM loop.
The Address setting tool 3314 is also used for mode setting:
NORMAL mode
: 4300 in this mode is in WinG3, for the
smoke detector, set to one of six algorithms H-15, H-35, L-15,
L-35,
N-15
or N-35 and for the heat detector set to one of three
algorithms for class
A1
(static response temp. 54-65°C), A2 S
(54-70°C) or B S (69-85°C).
2330 mode
: Not used in system EBL512 G3.
2312 mode
: Not used in system EBL512 G3.
4301
Analog photo electric smoke detector. Scattered light (i.e.
reflection of infrared light) is used to detect smoke.
The detector has unleaded soldering.
Shall be plugged in an analog base (3312 / 3312F / 3312FL /
4313). Built-in LEDs are lit to indicate that the detector has
activated fire alarm. Prepared for mechanical lock (screw
attached) – if required.
The COM loop address is set with the Address setting tool
(3314). The detector has an address label on which the
programmed COM loop address can be written.