Panasonic Electric Works Nordic AB
MEW01351
Rev: -
Planning Instructions Fire alarm system EBL512 G3, V1.1.x
31
Input 0
(J1:3-4): Can be used for German Fire alarm routing
equipment fault
(Melder quittung)
Input 1
(J1:7-8): Can be used for German key cabinet
(FSK
rückmeldung)
Input 2
(J1:9-10): Can be used for German key cabinet
(FSK
überwachung)
Input 3
(J1:13-14): Can be used for German extinguishing system
(Löschanlage ausgelöst)
Input 4
(J1:15-16): Can be used for German extinguishing system
(Löschanlage quittung)
See also the WinG3 help or chapter "Programmable inputs", page 62.
6.5
I/O Matrix board 4582
A special type of expansion board that only can be used together with
an
Application board
(e.g. Fan, Generic or Zone), see pages 26 and
52. The I/O Matrix board makes it possible for any retailer to
manufacture and connect three different types of "Application boards"
to EBL512 G3 via the COM loop.
Figure 6. I/O Matrix board application
overview
. The COM
loop and 24 V DC are internally connected to the I/O Matrix
board.
The I/O Matrix board (80 x 63 mm) is plugged to the Application
board respectively ("piggy back" connection) and has 16 switch inputs
and 48 LED outputs. The COM loop and 24 V DC is connected to the
Application board.
Three different
application board types
can be selected via jumpers
(
JP4-JP5
) on the I/O Matrix board:
Generic
control and indicating panel (Mimic panel alt. New
Zealand indication panel), with 16 inputs (any input trigger
condition can be used) and 48 outputs (any output trigger condition
can be used).
This type is used with the "General I/O application board" 4596.
I/O
Matrix
board
4582
EBL512 G3
C.i.e
.
COM loop
24 V DC
Type:
Generic
Fan
Generic
Fan control
Zone control
Application
boards:
Fan control with
4 Fan control panels
Mimic panel / New Zealand i.p.
Zone c.i.p.
No. 0
No. 1
No. 3
I/O
Matrix
board
4582
I/O
Matrix
board
4582
Zone