Planning Instructions Fire alarm system EBL512 G3, V1.1.x
106
The detectors in an AAF zone can be one to five and not be
programmed as 2-unit-dependent and not be controlled by the Alert
Annunciation function.
Only Analog photo electric smoke detector 4301 and Analog multi
detector 4300 can be used for AAF. If the Analog multi detector 4300
is used, it must be programmed as type "Two addresses", so that only
the "smoke part" of the detector can be used for AAF.
Max. 100 AAF zones (00-99) per c.i.e.
The AAF buzzer (e.g. Sounder base 3379) has to be programmed with
the trigger condition "AAF zone alarm" (and other trigger conditions).
16.14
Quiet alarm
Quiet alarm is normally used in conjunction with the I/O Matrix board
4582
99
, an application board for fan control
100
and an I/O unit 3361 for
fan control.
Smoke detectors, programmed for quiet alarm, can be used e.g. for
controlling fans (stop / start depending on the type of fan).
Indications and actions:
In the c.i.e. display:
Quiet alarm detector ZZZ-AA
and a user definable alarm text, if programmed.
LEDs "Fire" in the c.i.e. are blinking (0.4 / 0.4 sec.).
Buzzer in the c.i.e. sounding (0.8 / 5 sec.).
Programmable outputs for quiet alarm, e.g. 3361 outputs
controlling supply air fans and standard fans i.e. any output
with a control expression containing trigger conditions "Quiet
Alarm Zone" or "Quiet Alarm Zone Address".
Quiet alarms are non-latching, i.e. they will be automatically reset
when the alarm point / zone is no longer above alarm level.
NOTE!
Quiet alarm can also be programmed for a 3361 unit "zone
line input". In such a case only non-latching detectors can be used.
16.15
Fire alarm type A and Fire alarm type B
Normally the c.i.e. relay output "Fire alarm" is used for Fire alarm
routing equipment (Fire brigade tx). This output is activated for fire
alarm from any alarm point or zone line input (General fire alarm).
If the fire alarm routing equipment has provision for transmission of
several fire alarm signals and the alarm receiver has provision for
reception of several fire alarm signals, a fire alarm type B will indicate
that only one detector is activated, which
could
be a nuisance alarm.
99
See "I/O Matrix board 4582", page 30.
100
The Fan control panel 4593 can be used for control of up to eight fans.