Planning Instructions Fire alarm system EBL512 G3, V1.1.x
108
shall not be selected, see chapter "System properties, Page 2", page
133.
NOTE!
Enhanced Disablement is NOT valid when a time channel is
used for disablements, only when menu H2/B1 or B2 is used.
16.16.1
Disable zone
A whole zone (all addresses within a zone, except the manual call
points) can be disabled via menu H2/B1. Re-enabled via menu
H2/B4.
16.16.2
Disable zone / address
Individual alarm points can be disabled via menu H2/B2. Re-enabled
via menu H2/B5.
Time channels can be used to disable and re-enable automatically.
16.16.3
Disable control output
All outputs (except outputs of type "Alarm Device") can be
individually disabled via menu H2/B3. Re-enabled via menu H2/B6.
Disabled output will stay in (or return to) the normal condition for the
output respectively.
16.16.4
Disable / Re-enable output type
The control outputs can be collective disabled via menu H2/B7, type:
"Control (general)"
"Extinguishing"
"Ventilation"
"Control/exting./vent.
"Interlocking"
It is possible to do this for one or more specific control units or for all
control units (i.e. the whole system). Re-enabled via menu H2/B7.
Disabled outputs will stay in (or return to) the normal condition for the
output respectively.
16.16.5
Disable / Re-enable alarm devices
The control outputs of type "Alarm device (sounder)" can be
collective disabled via menu H2/B8. It is only possible to do this for
all control units (i.e. the whole system). Re-enabled via menu H2/B8.
Disabled outputs will stay in (or return to) the normal condition for the
output respectively.
16.17
Disable interlocking output
Individually disabled via menu H9/C4. Re-enabled via menu H9/C5.
See also chapter "Disable interlocking output (H9/C4)", page 87.
16.18
Disable outputs for routing equipment
Disabled and Re-enabled via menu H2/B9. For more information see
EBL512 G3 Operating Instructions MEW01163.