Planning Instructions Fire alarm system EBL512 G3, V1.1.x
45
6295
Heat detector: Enclosed (IP67)
29
. Fixed temperature heat
detector, 57°C, class
A2 S
(static response temp. range 54-
70°C), latching.
Min./
typical
/max. ambient temp. -40/
+25
/+50°C. Built-in LED
is lit to indicate that the detector has activated a fire alarm.
Terminals for an ext. LED (2218).
6296
Heat detector: Enclosed (IP67)
30
. Like 6295 but 72°C, class
B
S
(static response temp. range 69-85°C), latching.
Min./
typical
/max. ambient temp. -40/
+40
/+65°C. Built-in LED
is lit to indicate that the detector has activated a fire alarm.
Terminals for an ext. LED ( 2218).
6297
Heat detector: Enclosed (IP67). Like 6295 but 87°C, class
C S
(static response temp. range 84-100°C), latching.
Min./
typical
/max. ambient temp. -40/
+55
/+80°C. Built-in LED
is lit to indicate that the detector has activated a fire alarm.
Terminals for an ext. LED (2218).
6298
Heat detector: Enclosed (IP67). Like 6295 but 117°C, class
E S
(static response temp. range 114-130°C), latching.
Min./
typical
/max. ambient temp. -40/
+85
/+110°C.
No
built-in
LED but terminals for an ext. LED (2218) - to indicate that the
detector has activated a fire alarm.
9.1.1.6
Accessories
3314
Address setting tool. Is used to write or read the units'
COM
loop address
(Technical address 001-255). It is also used to
write or read the mode, see the unit respectively. In system
EBL512 G3 shall
NORMAL
mode always be used. A
connection cable with crocodile clips and tab terminals is
supplied with the tool and can be used when required.
Put the ON/OFF switch in position ON and wait for a beep.
Plug the detector's SA & SB terminals onto the tool's SA & SB
terminals or, when required, use the connection cable.
31
How to read: Press "READ", wait for a beep and read the
address and mode.
How to write: To select the mode, press "WRITE" and
"READ" at the same time
and/or
write the address. Press
"WRITE" and wait for a beep. ("READ" again as a check.)
29
This detector holds the ATEX classification:
Ex II 3GD EEx nA II T5 (T 100°C), -40°C < T
a
< 50°C
.
30
This detector holds the ATEX classification:
Ex II 3GD EEx nA II T5 (T 100°C), -40°C < T
a
< 65°C
.
31
Some units have flying leads for easier connection. After use they should
be disconnected and thrown away.