Planning Instructions Fire alarm system EBL512 G3, V1.1.x
109
16.19
Disconnect & Re-connect loop / zone line
input
Disconnected via menu H8/S1 and Re-connected via menu H8/S2:
COM loop
Zone line input
Addr. zone interface (3361 zone line input)
For more information see EBL512 G3 Operating Instructions
MEW01163.
16.20
External time channels 15-63
External time channels can be used to:
disable and re-enable alarm points
turn the Alert Annunciation function on/off
activate programmable control outputs
turn Alternative alarm algorithm for analog detector types 430x
on/off
turn the 2-unit dependence function on/off
The external time channels 15-63 are for the whole system. One
programmable input with trigger condition/type "External Time
Channel" is used for each external time channel, which also is given a
"Name". The input is controlled by some external equipment, e.g.
another time system, a key switch, a timer, etc. with a normally open
contact (normally low) or a normally closed contact (normally high).
When the input is "activated" the time channel is ON.
NOTE!
You must not use more than one input per time channel.
(This is checked in the "Validity check" in WinG3).
16.21
Test mode
Up to four zones can be set in Test mode at the same time. Alarm
points / zones can be tested during the Monthly test via menu H1 or
separately via menu H7. For more information see EBL512 G3
Operating Instructions MEW01163. The LED "Test mode" on the
c.i.e. front indicates one or more zones in Test mode. Zones in Test
mode are also simultaneously shown in the c.i.e. display.
Disablements, faults and fire alarms have higher priority, i.e. the
presentation of zones in Test mode will be suppressed during such a
condition. In order to shorten the testing time, any time delay before
alarm will be "turned off" in Test mode.
102
16.22
Test alarm devices
The programmable outputs of type "Alarm device" can be collectively
activated via menu H8/S5, which make it possible to test the alarm
102
The test mode alarm will be activated at the pre-warning level. Any 2-
zone / -address dependence and the function "delayed alarm" will be ignored.