Planning Instructions Fire alarm system EBL512 G3, V1.1.x
15
is space for two 28 Ah batteries. Larger batteries (up to 65 Ah) have
to be placed outside the c.i.e.
The batteries and the power supply are connected to the Main board
(5010), which handles the charging of the batteries, etc. See chapter
"Power supply", page 152 for more information.
3.2
S/W versions
Due to continual development and improvement, different S/W
versions can be found. When installing a new control unit in a system
with "older" control units, you might have to update the S/W in the
old control units (or download an older version in the new control
unit). T
he same S/W version is required in all control units
in a
TLON network.
3.3
Documents
The following documents are available:
Planning Instructions
Operating Instructions MEW01163
Drawings
Normally, information found in one of the documents is not found in
another document, i.e. the documents complement each other.
3.4
Applications
The EBL512 G3 system is intended for small, medium and large
installations. The intelligent control units offer the system designer
and end user a technically sophisticated range of facilities and
functions. Programming (PC software WinG3 and TLON Manager)
and commissioning of the control units / system is very easy.
Start with one control unit and then later when it is required, add more
units. The TLON network makes it possible to install the control units
in one building or in many buildings.
3.5
PC software (S/W)
The following PC software is used together with the EBL512 G3
system.
3.5.1
WinG3
WinG3
is used for programming and commissioning of one or more
control units, i.e. to:
create and download / make a backup of site specific data (SSD)
download new software / settings / conventions / configurations /
control unit & system properties / etc.
create and download the user definable alarm text messages
shown in the display in the control units / ext. FBPs and other
Display Units.