Panasonic Electric Works Nordic AB
MEW01351
Rev: -
Planning Instructions Fire alarm system EBL512 G3, V1.1.x
131
20
System properties (settings)
Figure 26. The WinG3 "System properties" dialog box, Page 1 and Page 2.
NOTE!
Default settings in WinG3 might vary depending on
convention.
20.1
System properties dialog box
Opens via the "System" pop-up menu or via menu "System"
(Properties...).
20.1.1
Name
Normally the name of the installation.
20.1.2
User definable text
For user definable text. Two rows á 40 characters are available. The
text will be shown in all control units. For more information see
EBL512 G3 Operating Instructions MEW01163.
20.1.3
System properties, Page 1
20.1.3.1
Alert Annunciation
See also chapter "Alert Annunciation", page 102.
Acknowledgement time
: 30
sec.
30 is default. 0-120 (= 2 min.) is possible.
Investigation time
: 3
min.
3 is default. 0-9 is possible.
NOTE!
According to EN54-2, the total delay of fire alarm routing
equipment (Acknowledge time + Investigation time) must not exceed
10 minutes.
Number of zones
: 1
1 is default. 1-4 is possible.
Multiple alarms allowed within same zone
Normally only one Alert Annunciation alarm is allowed within the
zone. If more Alert Annunciation alarms within the zone are
allowed, this checkbox shall be marked.