Fan control functions. The panel is intended to be mounted in
the General control cabinet
4590
, in which three Fan control
panels
4593
can be mounted. For connection to the c.i.e. is one
I/O Matrix board
4582
required for each 4594 board. Each
4594 board is connected to a COM loop and 24 V DC. Up to
eight panels (i.e. sixteen 4594 with 4582) can be used. One I/O
unit 3361 is also required for each fan. For more information,
see Technical Description MEW01245.
4596
General I/O application board. The board has connectors for 16
push button
inputs (programmable) and 48
LED
outputs
(programmable). The board is intended to be mounted in the
General control cabinet 4590, e.g. on the back-side of a
mounting panel. 4596 is mounted on an aluminium mounting
plate provided with a DIN-rail clamp for a 35 mm symmetric
DIN-rail. In 4590 can three mounting panels be mounted. For
connection to the c.i.e. is one I/O Matrix board 4582 required.
Each 4596 board is connected to a COM loop and 24 V DC.
Up to sixteen 4596 with 4582 can be used. For more
information, see Technical Description MEW01246.
4601
Wireless photoelectric smoke detector.
40
The detector is
plugged in an attached base and the colour is white. Latest IC
technology will secure the highest reliability possible. The
smoke detection chamber contains an IR LED and a
photodiode. Scattered light (i.e. reflection of infrared light) is
used to detect smoke. The smoke enters the detection chamber
through an insect filter and an optical labyrinth. Fire alarm will
be activated after three values over the fire alarm threshold
level. The detector has sensitivity compensation for
contamination. Transmission distance between Detector and
Base station is min. 40 m in open air. The Wireless smoke
detector is power supplied by three pieces of a 3 V Lithium
2400 mAh battery, type 4602. The battery life time is more
than three years.
Up to 16 Wireless photoelectric smoke detectors (4601) can be
"connected" to an
Addressable Base station for wireless units
(4610). Each wireless detector shall be programmed like the
Analog photoelectric smoke detector (4301) regarding
presentation number (Zone-Address), alarm text, etc. For more
information, see the Technical Description and the Product
Leaflet.
4610
Addressable Base station for wireless units.
40
The Base station
consists of a p.c.b. mounted in a white plastic housing, which
has a great number of cable inlets and mounting holes. It has
fast connectors for the COM loop (in / out) and 24 V DC power
supply respectively. Up to four Base stations can be connected
to a COM loop in the EBL system and up to 16 (detector
address 0-15) Wireless photoelectric smoke detectors (4601)