4-25
4-2 Function Mode
4
Functions
<Group B: Detailed Function Parameters>
Momentary Power Interruption/Trip Retry (Restart)
This function allows you to determine the operation performed when a trip occurs due to momentary
power interruption, undervoltage, overcurrent, or overvoltage.
Set the retry condition according to your system.
Trip Retry Function
• Select the retry function during operation in [b001] (01 or 02). If [b005] is 00 (default), the following
operations are to be performed.
At the time of momentary power interruption and undervoltage: Restarts 16 times and trips on
the 17th time.
At the time of overcurrent and overvoltage: Restarts 3 times respectively and trips on the 4th
time.
Retry times are counted separately for momentary power interruption, undervoltage, overcurrent,
and overvoltage. For example, an overvoltage trip occurs only after 3-time overcurrent trips and
then 4-time overvoltage trips. For momentary power interruption and undervoltage, if [b005] is set
to 01, the retry operation continues until the status is cleared.
• You can select the operation for momentary power interruption and undervoltage during stop in
b004.
(Supplemental Information)
Frequency matching start: Restarts the motor without stopping it after matching the motor rotation
speed. (If the RUN command is set on the Digital Operator (A002 = 2),
the Inverter stops.)
Parameter No.
Function name
Data
Default setting
Unit
b001
Retry selection
00: Outputs an alarm after a trip.
01: Restarts from 0 Hz at retry.
02: Matches the frequency at retry and
starts.
03: Performs frequency pull-in start at retry
and trips after deceleration stop.
00
b002
Allowable momentary
power interruption time
0.3 to 25.0
Trips if the momentary power interruption is
within the set time. If not, it restarts.
1.0
s
b003
Retry wait time
0.3 to 100.0
Time from recovery to restart
1.0
s
b004
Momentary power
interruption/undervoltage
trip during stop selection
00: Disabled
01: Enabled
00
b005
Momentary power
interruption retry time
selection
00: 16 times
01: No limit
00
Related functions
C021 to C022, C026
Summary of Contents for SYSDRIVE 3G3MX-A2002
Page 1: ...Cat No I559 E1 01 USER S MANUAL SYSDRIVE MXSERIES Multi function Compact Inverter...
Page 17: ...Chapter 1 Overview 1 1 Functions 1 1 1 2 Appearance and Names of Parts 1 3...
Page 24: ......
Page 25: ...Chapter 2 Design 2 1 Installation 2 1 2 2 Removing and Mounting Each Part 2 5 2 3 Wiring 2 10...
Page 90: ......
Page 91: ...Chapter 4 Functions 4 1 Monitor Mode 4 1 4 2 Function Mode 4 5...
Page 180: ......
Page 181: ...Chapter 5 Maintenance Operations 5 1 Special Display List 5 1 5 2 Troubleshooting 5 5...
Page 188: ......
Page 189: ...Chapter 6 Inspection and Maintenance 6 1 Inspection and Maintenance 6 1 6 2 Storage 6 7...
Page 212: ...7 15 7 5 Options 7 Specifications 3G3AX RBU41 95 75 2 5 208 218 5 145 35 100 5...
Page 230: ......
Page 231: ...Appendix Appendix 1 Parameter List App 1 Appendix 2 Product Life Curve App 17...
Page 249: ...INDEX...
Page 252: ......