2-27
2-3 Wiring
2
Design
*1. By factory default, multi-function output terminals, [P1] and [P2] are set to NO contact. To switch to NC contact,
change the C031 and C032 settings. In addition, these terminals are reset to NO contact when initialized.
*2.The factory default setting (C036) of the relay output terminals (MA, MB-MC) is set to NC contact.
In addition, these terminals are reset to NC contact when initialized.
To use the Inverter as an alternative to a conventional model or for built-in use with a system, check the
contact logic of the relay output terminal setting (C036), and match the logic with that of the peripheral circuit
before use. If these contact logics conflict with each other, a system breakdown may occur.
*3. Output terminal status
*4. Contact specifications
C036 set value
Power
supply
Output
signal
Output terminal status
MA-MC
MB-MC
00
ON
ON
Closed
Open
OFF
Open
Closed
OFF
Open
Closed
01
(Factory default)
ON
ON
Open
Closed
OFF
Closed
Open
OFF
Open
Closed
Output terminal
Resistance load
Inductive load
MA-MC
Max.
250 V AC, 2 A
30 V DC, 3 A
250 V AC, 0.2 A
30 V DC, 0.6 A
Min.
100 V AC, 10 mA
5 V DC, 100 mA
MB-MC
Max.
250 V AC, 1 A
30 V DC, 1 A
250 V AC, 0.2 A
30 V DC, 0.2 A
Min.
100 V AC, 10 mA
5 V DC, 100 mA
Summary of Contents for SYSDRIVE 3G3MX-A2002
Page 1: ...Cat No I559 E1 01 USER S MANUAL SYSDRIVE MXSERIES Multi function Compact Inverter...
Page 17: ...Chapter 1 Overview 1 1 Functions 1 1 1 2 Appearance and Names of Parts 1 3...
Page 24: ......
Page 25: ...Chapter 2 Design 2 1 Installation 2 1 2 2 Removing and Mounting Each Part 2 5 2 3 Wiring 2 10...
Page 90: ......
Page 91: ...Chapter 4 Functions 4 1 Monitor Mode 4 1 4 2 Function Mode 4 5...
Page 180: ......
Page 181: ...Chapter 5 Maintenance Operations 5 1 Special Display List 5 1 5 2 Troubleshooting 5 5...
Page 188: ......
Page 189: ...Chapter 6 Inspection and Maintenance 6 1 Inspection and Maintenance 6 1 6 2 Storage 6 7...
Page 212: ...7 15 7 5 Options 7 Specifications 3G3AX RBU41 95 75 2 5 208 218 5 145 35 100 5...
Page 230: ......
Page 231: ...Appendix Appendix 1 Parameter List App 1 Appendix 2 Product Life Curve App 17...
Page 249: ...INDEX...
Page 252: ......