![background image](http://html1.mh-extra.com/html/omron/sysdrive-3g3mx-a2002/sysdrive-3g3mx-a2002_user-manual_742838103.webp)
4-12
4-2 Function Mode
4
Func
tions
* To switch to the 2nd control, allocate 08 (SET) to the multi-function input and then turn it on.
Control Method (V/f Characteristics)
Constant Torque Characteristics (VC)
• Output voltage is proportional to output frequency.
While proportional from 0 Hz to base frequency, the output voltage is constant from base to
maximum frequencies regardless of the frequency.
Special Reduced Torque Characteristics (Special VP)
• Suitable for a fan or pump that requires torque in a low speed range. These have VC
characteristics only for low deceleration in reduced torque characteristics.
Period a: Provides constant torque characteristics (VC) within a range from 0 Hz to 10% of the base
frequency.
(Example) If the base frequency is 60 Hz, the Inverter provides constant torque
characteristics within a range from 0 to 6 Hz.
Period b: Provides reduced torque characteristics within a range from 10% to 100% of the base
frequency.
The Inverter outputs voltage based on a curve of the 1.7th power of the frequency.
Period c: Provides constant voltage within a range from the base frequency to the maximum
frequency.
A044
V/f characteristics selection
00: Constant torque characteristics
(VC)
01: Special reduced torque
characteristics (Special VP)
02: Intelligent sensorless vector control
(iSLV)
00
A244
* 2nd V/f characteristics
selection
A045
Output voltage gain
20. to 100.
100.
%
A245
*2nd output voltage gain
Related functions
A046, A246, A047, A247, A082,
H003, H203, H004, H204
Parameter No.
Function name
Data
Default setting
Unit
0
Output voltage
(100%)
Base frequency
(A003/A203)
Output frequency (Hz)
Max. frequency
(A004/A204)
0
Output voltage
(100%)
Base frequency
(A003/A203)
Output frequency (Hz)
Max. frequency
(A004/A204)
VC
VP (1.7th
power of VP)
10% of base
frequency
a
b
c
Summary of Contents for SYSDRIVE 3G3MX-A2002
Page 1: ...Cat No I559 E1 01 USER S MANUAL SYSDRIVE MXSERIES Multi function Compact Inverter...
Page 17: ...Chapter 1 Overview 1 1 Functions 1 1 1 2 Appearance and Names of Parts 1 3...
Page 24: ......
Page 25: ...Chapter 2 Design 2 1 Installation 2 1 2 2 Removing and Mounting Each Part 2 5 2 3 Wiring 2 10...
Page 90: ......
Page 91: ...Chapter 4 Functions 4 1 Monitor Mode 4 1 4 2 Function Mode 4 5...
Page 180: ......
Page 181: ...Chapter 5 Maintenance Operations 5 1 Special Display List 5 1 5 2 Troubleshooting 5 5...
Page 188: ......
Page 189: ...Chapter 6 Inspection and Maintenance 6 1 Inspection and Maintenance 6 1 6 2 Storage 6 7...
Page 212: ...7 15 7 5 Options 7 Specifications 3G3AX RBU41 95 75 2 5 208 218 5 145 35 100 5...
Page 230: ......
Page 231: ...Appendix Appendix 1 Parameter List App 1 Appendix 2 Product Life Curve App 17...
Page 249: ...INDEX...