4-83
4-2 Function Mode
4
Functions
0084h
FI start frequency
A101
R/W
0 to Max. frequency
0.1 [Hz]
0085h
FI end frequency
A102
R/W
0 to Max. frequency
0.1 [Hz]
0086h
FI start ratio
A103
R/W
0 to 100
1. [%]
0087h
FI end ratio
A104
R/W
0 to 100
1. [%]
0088h
FI start selection
A105
R/W
0: External start frequency
1: 0 Hz
0089h
Retry selection
b001
R/W
0: Alarm
1: 0-Hz start
2: Frequency matching start
3: Trip after frequency matching
deceleration stop
008Ah
Allowable momentary
power interruption time
b002
R/W
3 to 250
0.1 [s]
008Bh
Retry wait time
b003
R/W
3 to 1000
0.1 [s]
008Ch
Momentary power
interruption/undervoltage
trip during stop selection
b004
R/W
0: Disabled
1: Enabled
008Dh
Momentary power
interruption retry time
selection
b005
R/W
0: 16 times
1: No limit
008Eh
Electronic thermal level
b012
R/W
2000 to 12000
0.01 [%]
008Fh
2nd electronic thermal level
b212
R/W
2000 to 12000
0.01 [%]
0090h
Electronic thermal
characteristics selection
b013
R/W
0: Reduced torque characteristics 1
1: Constant torque characteristics
2: Reduced torque characteristics 2
*1
0091h
2nd electronic thermal
characteristics selection
b213
R/W
0: Reduced torque characteristics 1
1: Constant torque characteristics
2: Reduced torque characteristics 2
*1
0092h
Overload limit selection
b021
R/W
0: Disabled
1: Enabled during acceleration/constant
speed
2: Enabled during constant speed
0093h
Overload limit level
b022
R/W
5000 to 15000
*1
0.01 [%]
0094h
Overload limit parameter
b023
R/W
1 to 300
0.1 [s]
0095h
Soft lock selection
b031
R/W
0: Data other than b031 cannot be
changed when terminal SFT is ON.
1: Data other than b031 and the specified
frequency parameter cannot be
changed when terminal SFT is ON.
2: Data other than b031 cannot be
changed.
3: Data other than b031 and specified
frequency parameter cannot be
changed.
0096h
AM adjustment
b080
R/W
0 to 255
1
Register
No.
Function name
Parameter
No.
R/W
function
Data
Resolution
*1. The Inverter's rated current is "1000".
*2. The second decimal place is ignored when the value is over 10000 (100.0 seconds).
Summary of Contents for SYSDRIVE 3G3MX-A2002
Page 1: ...Cat No I559 E1 01 USER S MANUAL SYSDRIVE MXSERIES Multi function Compact Inverter...
Page 17: ...Chapter 1 Overview 1 1 Functions 1 1 1 2 Appearance and Names of Parts 1 3...
Page 24: ......
Page 25: ...Chapter 2 Design 2 1 Installation 2 1 2 2 Removing and Mounting Each Part 2 5 2 3 Wiring 2 10...
Page 90: ......
Page 91: ...Chapter 4 Functions 4 1 Monitor Mode 4 1 4 2 Function Mode 4 5...
Page 180: ......
Page 181: ...Chapter 5 Maintenance Operations 5 1 Special Display List 5 1 5 2 Troubleshooting 5 5...
Page 188: ......
Page 189: ...Chapter 6 Inspection and Maintenance 6 1 Inspection and Maintenance 6 1 6 2 Storage 6 7...
Page 212: ...7 15 7 5 Options 7 Specifications 3G3AX RBU41 95 75 2 5 208 218 5 145 35 100 5...
Page 230: ......
Page 231: ...Appendix Appendix 1 Parameter List App 1 Appendix 2 Product Life Curve App 17...
Page 249: ...INDEX...