![background image](http://html1.mh-extra.com/html/omron/sysdrive-3g3mx-a2002/sysdrive-3g3mx-a2002_user-manual_742838143.webp)
4-52
4-2 Function Mode
4
Func
tions
Forced Terminal Block Function
This function forcibly switches to operation via the terminal block by turning on/off the multi-function
terminal when the frequency reference/RUN command sources are not set to the terminal block.
• When the input of this signal is reset, A001 and A002 return to the command status prior to the
input.
• If you switch on/off this function during operation, the RUN command is reset to stop the Inverter.
Before resuming operation, stop the RUN command from each command source to avoid possible
danger and then input it again.
Ready Function
• Inputting this signal shortens the time between the RUN command input and the start of actual
operation. In normal status, this is approx. 20 ms. Shortened time through this function varies
depending on timing.
When the Inverter is in ready status, high voltage is applied to terminals U, V, and W on the main
circuit terminal block. This happens even if the motor is stopped with the RUN command turned off.
Do not touch the main circuit terminal block.
Σ
+
+/–
A145
FREQ adjuster
Terminal block
F001 set value
ModBus communication
Logic operation output
Frequency addition
Multi-function input
Frequency reference source
A001
[ADD]
Output frequency setting
Frequency addition direction setting
A146
Data
Symbol
Function name
Status
Description
51
F-TM
Forced terminal block
ON
Forcibly sets to A001 = 01 and A002 = 01.
OFF
Operates according to the A001 and A002 settings.
Available input terminals
C001, C002, C003, C004, C005, C006
Required settings
A001, A002
Data
Symbol
Function name
Status
Description
52
RDY
Ready function
ON
The Inverter is ready.
OFF
Normal stop status
Available input terminals
C001, C002, C003, C004, C005, C006
Summary of Contents for SYSDRIVE 3G3MX-A2002
Page 1: ...Cat No I559 E1 01 USER S MANUAL SYSDRIVE MXSERIES Multi function Compact Inverter...
Page 17: ...Chapter 1 Overview 1 1 Functions 1 1 1 2 Appearance and Names of Parts 1 3...
Page 24: ......
Page 25: ...Chapter 2 Design 2 1 Installation 2 1 2 2 Removing and Mounting Each Part 2 5 2 3 Wiring 2 10...
Page 90: ......
Page 91: ...Chapter 4 Functions 4 1 Monitor Mode 4 1 4 2 Function Mode 4 5...
Page 180: ......
Page 181: ...Chapter 5 Maintenance Operations 5 1 Special Display List 5 1 5 2 Troubleshooting 5 5...
Page 188: ......
Page 189: ...Chapter 6 Inspection and Maintenance 6 1 Inspection and Maintenance 6 1 6 2 Storage 6 7...
Page 212: ...7 15 7 5 Options 7 Specifications 3G3AX RBU41 95 75 2 5 208 218 5 145 35 100 5...
Page 230: ......
Page 231: ...Appendix Appendix 1 Parameter List App 1 Appendix 2 Product Life Curve App 17...
Page 249: ...INDEX...
Page 252: ......