4-37
4-2 Function Mode
4
Functions
Regenerative Braking Function
• With the built-in regenerative braking circuit, this function allows an external braking resistor to
consume the motor's regeneration energy as heat.
This function is useful for a system in which the motor works as a generator when it is rapidly
decelerated.
• To use this function, configure the following settings.
* The regenerative braking function ON level conforms to the voltage setting for the Inverter's internal converter
(DC unit).
• When using the regenerative braking function, mount the optional braking resistor between
terminals P/+2 and RB, in addition to the settings above.
* The above usage rate of the regenerative braking function is the figure for using the optional braking resistor
(3G3AX-RBA, RBB, RBC).
• When using an external regenerative braking unit, set the usage rate of the regenerative braking
function to 0.0% (b090: 0.0) or disable the regenerative braking function selection (b095: 00). Do
not mount the braking resistor between terminals P/+2 and RB.
Parameter No. Function name
Data
Default setting
Unit
b090
Usage rate of
regenerative
braking
function
00: Does not operate.
01 to 100.0:
A BRD usage rate for 100 seconds can be set, in
increments of 0.1%.
If the set usage rate is exceeded, a braking resistor
overload trip (E06) occurs.
0.0
%
b095
Regenerative
braking
function
operation
selection
00: Disabled (This function is not active.)
01: Enabled during operation (This function is
active.)
Disabled during stop (This function is not
active.)
02: Enabled during both operation and stop (This
function is active.)
0.0
b096
Regenerative
braking
function ON
level
200-V class: 330 to 380
*
400-V class: 660 to 760
*
(Inverter DC voltage)
200-V class: 360 V
400-V class: 720 V
V
t1
t2
t3
ON
ON
ON
BRD
operation
100 s
Usage rate (%) =
(t1 + t2 + t3)
100 s
× 100
Model
200-V class
400-V class
2002
2004
2007
2015
2022
2037
2055
2075
4004
4007
4015
4022
4037
4055
4075
Minimum resistance
(recommended)
100
Ω
50
Ω
35
Ω
17
Ω
180
Ω
100
Ω
70
Ω
Usage rate of regenerative
braking function
*
10%
Summary of Contents for SYSDRIVE 3G3MX-A2002
Page 1: ...Cat No I559 E1 01 USER S MANUAL SYSDRIVE MXSERIES Multi function Compact Inverter...
Page 17: ...Chapter 1 Overview 1 1 Functions 1 1 1 2 Appearance and Names of Parts 1 3...
Page 24: ......
Page 25: ...Chapter 2 Design 2 1 Installation 2 1 2 2 Removing and Mounting Each Part 2 5 2 3 Wiring 2 10...
Page 90: ......
Page 91: ...Chapter 4 Functions 4 1 Monitor Mode 4 1 4 2 Function Mode 4 5...
Page 180: ......
Page 181: ...Chapter 5 Maintenance Operations 5 1 Special Display List 5 1 5 2 Troubleshooting 5 5...
Page 188: ......
Page 189: ...Chapter 6 Inspection and Maintenance 6 1 Inspection and Maintenance 6 1 6 2 Storage 6 7...
Page 212: ...7 15 7 5 Options 7 Specifications 3G3AX RBU41 95 75 2 5 208 218 5 145 35 100 5...
Page 230: ......
Page 231: ...Appendix Appendix 1 Parameter List App 1 Appendix 2 Product Life Curve App 17...
Page 249: ...INDEX...
Page 252: ......