3-12
3-4 Operation Procedure (Example: Factory Default)
3
Opera
tion
Setting Functions
• Switch the method of the RUN command. (Digital Operator
→
Control terminal block)
• To switch the method of the RUN command from the Digital Operator (factory default) to the control
terminal block, you need to change the frequency reference selection (A001) from the Digital
Operator (02) to the terminal (01).
1. Display the extended function mode (as "A---").
• To display "A---", follow the indication method
• By default, the RUN command LED indicator will
light up as the RUN command source is set to
the Digital Operator.
2. The code of the extended function mode is displayed (as "A001").
("A002" is displayed.)
3. The setting of the extended function mode is displayed (setting in "A002").
• "02 (Digital Operator)" (default setting) is
displayed in the RUN command source (A002).
• The PROGRAM (PRG) LED indicator lights up
while the extended function mode setting is
displayed.
(Continued to the next page)
ak-k-k-
Press .
ak0k0k1
Press .
ak0k0k2
Press .
0k2
Press .
Summary of Contents for SYSDRIVE 3G3MX-A2002
Page 1: ...Cat No I559 E1 01 USER S MANUAL SYSDRIVE MXSERIES Multi function Compact Inverter...
Page 17: ...Chapter 1 Overview 1 1 Functions 1 1 1 2 Appearance and Names of Parts 1 3...
Page 24: ......
Page 25: ...Chapter 2 Design 2 1 Installation 2 1 2 2 Removing and Mounting Each Part 2 5 2 3 Wiring 2 10...
Page 90: ......
Page 91: ...Chapter 4 Functions 4 1 Monitor Mode 4 1 4 2 Function Mode 4 5...
Page 180: ......
Page 181: ...Chapter 5 Maintenance Operations 5 1 Special Display List 5 1 5 2 Troubleshooting 5 5...
Page 188: ......
Page 189: ...Chapter 6 Inspection and Maintenance 6 1 Inspection and Maintenance 6 1 6 2 Storage 6 7...
Page 212: ...7 15 7 5 Options 7 Specifications 3G3AX RBU41 95 75 2 5 208 218 5 145 35 100 5...
Page 230: ......
Page 231: ...Appendix Appendix 1 Parameter List App 1 Appendix 2 Product Life Curve App 17...
Page 249: ...INDEX...
Page 252: ......