3-2
3-1 Test Run Procedure
3
Opera
tion
3-1 Test Run Procedure
• Make sure that the installation conditions are met.
• Select peripheral devices that meet the specifications, and wire correctly.
• Make sure that an appropriate power supply voltage is supplied and that the power input
terminals (R/L1, S/L2, and T/L3) are wired correctly.
3G3MX-A2
: 3-phase 200 to 240 V AC
3G3MX-AE
: 1/3-phase 200 to 240 V AC
(Connect to L1 and N/L3 for 1 phase)
3G3MX-A4
: 3-phase 380 to 480 V AC
• Make sure that the motor output terminals (U/T1, V/T2, and W/T3) are connected to the
motor correctly.
• Make sure that the control circuit terminals and the control device are wired correctly
and that all control terminals are turned off.
• Set the motor to a no-load state (i.e., not connected to the mechanical system).
• After checking the above, turn on the power.
• When the power is turned on normally, the display shows:
RUN LED indicator
: ON
ALARM LED indicator
: OFF
POWER LED indicator : ON
RUN command LED indicator
: ON
Volume LED indicator : ON
Data LED indicator (frequency) : ON
Data display
: Displays the set value in d001.
• If an error occurs, the error code is displayed on the data display. In this case, refer to
"
Chapter 5 Maintenance Operations
" and make the necessary changes to remedy.
• Set parameter b084 to "02", and press the
key while holding down the
,
,
and keys
simultaneously.
• Set the motor capacity selection (H003) and the motor pole number selection (H004).
• Use the FREQ adjuster on the Digital Operator to rotate the motor.
• If there are no difficulties with the no-load operation, connect the mechanical system to
the motor and operate via the Digital Operator.
Item
Description
Reference page
Installation and Mounting Install the Inverter according to the installation conditions.
Wiring and Connection
Connect to the power supply and peripheral devices.
Power On
Check the following before turning on the power.
Display Status Check
Make sure that there are no faults in the Inverter.
Parameter Initialization
Initialize the parameters.
Parameter Settings
Set the parameters required for a test run.
No-load Operation
Start the no-load motor via the Digital Operator.
Actual Load Operation
Connect the mechanical system and operate via the Digital Operator.
Operation
Refer to "Chapter 4 Functions", and set the necessary parameters.
Summary of Contents for SYSDRIVE 3G3MX-A2002
Page 1: ...Cat No I559 E1 01 USER S MANUAL SYSDRIVE MXSERIES Multi function Compact Inverter...
Page 17: ...Chapter 1 Overview 1 1 Functions 1 1 1 2 Appearance and Names of Parts 1 3...
Page 24: ......
Page 25: ...Chapter 2 Design 2 1 Installation 2 1 2 2 Removing and Mounting Each Part 2 5 2 3 Wiring 2 10...
Page 90: ......
Page 91: ...Chapter 4 Functions 4 1 Monitor Mode 4 1 4 2 Function Mode 4 5...
Page 180: ......
Page 181: ...Chapter 5 Maintenance Operations 5 1 Special Display List 5 1 5 2 Troubleshooting 5 5...
Page 188: ......
Page 189: ...Chapter 6 Inspection and Maintenance 6 1 Inspection and Maintenance 6 1 6 2 Storage 6 7...
Page 212: ...7 15 7 5 Options 7 Specifications 3G3AX RBU41 95 75 2 5 208 218 5 145 35 100 5...
Page 230: ......
Page 231: ...Appendix Appendix 1 Parameter List App 1 Appendix 2 Product Life Curve App 17...
Page 249: ...INDEX...
Page 252: ......