![background image](http://html1.mh-extra.com/html/omron/sysdrive-3g3mx-a2002/sysdrive-3g3mx-a2002_user-manual_742838144.webp)
4-53
4-2 Function Mode
4
Functions
Multi-function Output Selection
• You can allocate the following functions to multi-function output terminals P1, P2 and the relay
output terminals.
•Multi-function output terminals P1 to P2 provide open-collector output. The relay output terminal
provides SPDT contact relay output.
• You can select NO- or NC-contact output for each output terminal with C031 to C032 or C036.
Signal During RUN
This function outputs a signal while the Inverter is running.
Parameter No.
Function name
Data
Default setting
Unit
C021
Multi-function output
terminal P1 selection
00: RUN (signal during RUN)
01: FA1 (constant speed arrival signal)
02: FA2 (over set frequency arrival
signal)
03: OL (overload warning)
04: OD (excessive PID deviation)
05: AL (alarm output)
06: Dc (disconnection detected)
07: FBV (PID FB status output)
08: NDc (network error)
09: LOG (logic operation output)
10: ODc (communication option
disconnected)
00
C022
Multi-function output
terminal P2 selection
01
C026
Relay output (MA, MB)
function selection
05
Data
Description
Reference item
Page
00
RUN: Signal during RUN
Signal during RUN
01
FA1: Constant speed arrival signal
Frequency arrival signal
02
FA2: Over set frequency arrival signal
03
OL: Overload warning
Overload limit/Overload
warning
04
OD: Excessive PID deviation
PID function
05
AL: Alarm output
06
DC: Disconnection detection
External analog input
disconnection detection
07
FBV: PID FB status output
PID function
08
NDC: Network error
Network error
09
LOG: Logic operation output
Logic operation function
10
ODc: Communication option disconnected
Network signal error
Data
Symbol
Function name
Status
Description
00
RUN
Signal during RUN
ON
The Inverter is in RUN mode.
OFF
The Inverter is in STOP mode.
Available input terminals
P1-PC, P2-PC, MA-MC (or MB-MC)
Required settings
C021, C022, C026
Summary of Contents for SYSDRIVE 3G3MX-A2002
Page 1: ...Cat No I559 E1 01 USER S MANUAL SYSDRIVE MXSERIES Multi function Compact Inverter...
Page 17: ...Chapter 1 Overview 1 1 Functions 1 1 1 2 Appearance and Names of Parts 1 3...
Page 24: ......
Page 25: ...Chapter 2 Design 2 1 Installation 2 1 2 2 Removing and Mounting Each Part 2 5 2 3 Wiring 2 10...
Page 90: ......
Page 91: ...Chapter 4 Functions 4 1 Monitor Mode 4 1 4 2 Function Mode 4 5...
Page 180: ......
Page 181: ...Chapter 5 Maintenance Operations 5 1 Special Display List 5 1 5 2 Troubleshooting 5 5...
Page 188: ......
Page 189: ...Chapter 6 Inspection and Maintenance 6 1 Inspection and Maintenance 6 1 6 2 Storage 6 7...
Page 212: ...7 15 7 5 Options 7 Specifications 3G3AX RBU41 95 75 2 5 208 218 5 145 35 100 5...
Page 230: ......
Page 231: ...Appendix Appendix 1 Parameter List App 1 Appendix 2 Product Life Curve App 17...
Page 249: ...INDEX...
Page 252: ......