4-36
4-2 Function Mode
4
Func
tions
• Note that an overcurrent trip may occur if the mechanical brake forces the motor to stop during
Inverter output.
• Allocate 11 (FRS) to the desired multi-function input.
• Performs a free-run stop (FRS) while the FRS terminal is turned on.
When the FRS terminal is turned off, the motor restarts after retry wait time b003 elapses.
With RUN command selection A002 set to 01 (control terminal), the motor restarts only if the FW
terminal is turned on, even in free running.
• You can select the Inverter output mode for restart at free-run stop selection b088 (0 Hz start or
frequency matching restart). (Examples 1, 2)
• The setting of this function is also applied to stop selection b091.
Cooling Fan Control
• You can set whether to operate the Inverter's cooling fan constantly or only during Inverter
operation.
This function applies to the Inverter models with a built-in cooling fan.
(Example 1) 0 Hz start
FW
FRS
Motor rotation
speed
0
Free running
0 Hz start
(Example 2) Frequency matching start
FW
FRS
Motor rotation
speed
Free running
b003
0
Frequency matching start
· The Inverter starts running at 0 Hz regardless of the
motor rotation speed.
· The retry wait time is ignored at 0 Hz start.
· If the Inverter starts running at 0 Hz with the motor
rotation speed high, an overcurrent trip may occur.
· After the FRS terminal is turned off, the motor frequency
is matched and a frequency matching starts without stopping
the motor. If this causes an overcurrent trip, extend the retry
wait time.
Parameter No.
Function name
Data
Default setting
Unit
b092
Cooling fan control
00: Always ON
01: ON during RUN
02: Depends on the fin temperature
01
Data
Description
00
Operates constantly.
01
Operates only during RUN.
The cooling fan operates for 5 minutes after power-on, and for 5 minutes after the Inverter stops.
02
Operates when the fin temperature is 50
°
C or higher.
Summary of Contents for SYSDRIVE 3G3MX-A2002
Page 1: ...Cat No I559 E1 01 USER S MANUAL SYSDRIVE MXSERIES Multi function Compact Inverter...
Page 17: ...Chapter 1 Overview 1 1 Functions 1 1 1 2 Appearance and Names of Parts 1 3...
Page 24: ......
Page 25: ...Chapter 2 Design 2 1 Installation 2 1 2 2 Removing and Mounting Each Part 2 5 2 3 Wiring 2 10...
Page 90: ......
Page 91: ...Chapter 4 Functions 4 1 Monitor Mode 4 1 4 2 Function Mode 4 5...
Page 180: ......
Page 181: ...Chapter 5 Maintenance Operations 5 1 Special Display List 5 1 5 2 Troubleshooting 5 5...
Page 188: ......
Page 189: ...Chapter 6 Inspection and Maintenance 6 1 Inspection and Maintenance 6 1 6 2 Storage 6 7...
Page 212: ...7 15 7 5 Options 7 Specifications 3G3AX RBU41 95 75 2 5 208 218 5 145 35 100 5...
Page 230: ......
Page 231: ...Appendix Appendix 1 Parameter List App 1 Appendix 2 Product Life Curve App 17...
Page 249: ...INDEX...
Page 252: ......