Event name
Internal Circuit Error at Safety Output
Event code
05230000 hex
Meaning
A fault was detected in the internal circuit for the safety output terminal.
Source
Depends on where the Sysmac
Studio is connected and the sys-
tem configuration.
Source details
NX Unit
Detection tim-
ing
During refresh-
ing
Error attrib-
utes
Level
Minor fault
Recovery
Cycle the pow-
er supply to the
Unit.
Log category
System
Effects
User program
Continues.
Operation
The safety output terminal retains the safe state
until the power supply is cycled.
System-de-
fined varia-
bles
Variable
Data type
Name
None
None
None
Cause and
correction
Assumed cause
Correction
Prevention
The internal circuit for the safety
output terminal is faulty.
Cycle the power supply. If the er-
ror occurs again, replace the
Unit.
If cycling the power supply re-
stores normal operation, there
may be excessive noise near the
Unit. Implement noise counter-
measures.
A memory error or signal error
occurred due to a transient
cause, such as an excessive
noise.
Attached in-
formation
Attached information 1: Terminal number
Precautions/
Remarks
None
12 Troubleshooting
12 - 79
NX-series Safety Control Unit User's Manual (Z930)
12-3 Checking for Errors with the Sysmac Studio
12
12-3-4 Error Descriptions
Summary of Contents for NX-SIH400
Page 4: ...Introduction 2 NX series Safety Control Unit User s Manual Z930 ...
Page 46: ...Revision History 44 NX series Safety Control Unit User s Manual Z930 ...
Page 108: ...2 Specifications 2 42 NX series Safety Control Unit User s Manual Z930 ...
Page 132: ...3 Installation and Wiring 3 24 NX series Safety Control Unit User s Manual Z930 ...
Page 148: ...4 Safety Control Unit Operation 4 16 NX series Safety Control Unit User s Manual Z930 ...
Page 216: ...5 System Configuration and Setup 5 44 NX series Safety Control Unit User s Manual Z930 ...
Page 306: ...6 Programming 6 90 NX series Safety Control Unit User s Manual Z930 ...
Page 390: ...8 Calculating Safety Reaction Times 8 12 NX series Safety Control Unit User s Manual Z930 ...
Page 412: ...11 Safety Data Logging 11 10 NX series Safety Control Unit User s Manual Z930 ...
Page 504: ...12 Troubleshooting 12 92 NX series Safety Control Unit User s Manual Z930 ...
Page 554: ...l I O Map Settings Appendices A 42 NX series Safety Control Unit User s Manual Z930 ...
Page 623: ...I Index I 1 NX series Safety Control Unit User s Manual Z930 I ...
Page 625: ......