8-3-3
Settings for FSoE Watchdog Timers
This section describes how to find the set values for the FSoE watchdog timers.
The set value for an FSoE watchdog timer is different from the set value of the safety task period.
l
Safety Task Period < 100 ms
Set the FSoE watchdog timer to the same value as the expansion communications monitoring time
that you added to the safety task period.
l
Safety Task Period = 100 ms
Set the FSoE watchdog timer to a value that is an integer multiple of the safety task period.
8-3-4
Changing FSoE Watchdog Timers
Use the following procedure to change a FSoE watchdog timer.
1
In the Multiview Explorer, select the target Safety CPU Unit in the Controller Selection Box.
2
Double-click
Safety I/O
under
Configurations and Setup
–
Communications
–
Safety
.
The following Safety I/O Unit Setting Tab Page is displayed.
3
Clear the selection of the
WDT auto setting
Check Box for the Unit to change.
This enables changing the value of the
FSoE watchdog timer
.
4
Double-click the cell in the
FSoE watchdog timer
Column for the Unit to change and set the
desired FSoE watchdog timer value.
Version Information
You can change the FSoE watchdog timers with Sysmac Studio version 1.10 or higher.
8 Calculating Safety Reaction Times
8 - 10
NX-series Safety Control Unit User's Manual (Z930)
Summary of Contents for NX-SIH400
Page 4: ...Introduction 2 NX series Safety Control Unit User s Manual Z930 ...
Page 46: ...Revision History 44 NX series Safety Control Unit User s Manual Z930 ...
Page 108: ...2 Specifications 2 42 NX series Safety Control Unit User s Manual Z930 ...
Page 132: ...3 Installation and Wiring 3 24 NX series Safety Control Unit User s Manual Z930 ...
Page 148: ...4 Safety Control Unit Operation 4 16 NX series Safety Control Unit User s Manual Z930 ...
Page 216: ...5 System Configuration and Setup 5 44 NX series Safety Control Unit User s Manual Z930 ...
Page 306: ...6 Programming 6 90 NX series Safety Control Unit User s Manual Z930 ...
Page 390: ...8 Calculating Safety Reaction Times 8 12 NX series Safety Control Unit User s Manual Z930 ...
Page 412: ...11 Safety Data Logging 11 10 NX series Safety Control Unit User s Manual Z930 ...
Page 504: ...12 Troubleshooting 12 92 NX series Safety Control Unit User s Manual Z930 ...
Page 554: ...l I O Map Settings Appendices A 42 NX series Safety Control Unit User s Manual Z930 ...
Page 623: ...I Index I 1 NX series Safety Control Unit User s Manual Z930 I ...
Page 625: ......