Precautions for Correct Use
• The memory in the Safety CPU Unit is not cleared even if you right-click the Communications
Coupler Unit in the Slave Terminal Tab Page and select
Clear All Memory
for all Units. To
clear the memory of a Safety CPU Unit, use the Clear All Memory operation for NX Units.
• The memory in the Safety CPU Unit is not cleared even when you perform the Clear All
Memory operation for controllers. To clear the memory of the Safety CPU Unit, use the Clear
All Memory operation for NX Units.
• You can execute the Clear All Memory operation for a Safety CPU Unit only when the Safety
CPU Unit is in PROGRAM mode.
Scope of Data to Clear and State of Memory After It Is Cleared
l
Safety CPU Unit
Data item
Status after clear all memory operation
I/O allocation information
This data is set to the default settings (I/O size = 0 bytes).
Safety programs
This data is set to the default settings (no programs).
Safety password
This data is set to the default settings (no password).
Event logs
Event logs are cleared if you select the Clear the event logs Option when you
execute the Clear All Memory operation.
l
Safety I/O Units
Data item
Status after clear all memory operation
FSoE slave address
This data is set to the default setting (no setting).
Event logs
Event logs are cleared if you select the Clear the event logs Option when you
execute the Clear All Memory operation.
Precautions for Safe Use
After you clear the memory, the Controller operates in the same way as immediately after you
create the system configuration with the Controller in the factory default condition.
Procedure for Clear All Memory Operation
l
Clear All Memory Operation for NX Units
1
Go online, right-click a Safety CPU Unit or Safety I/O Unit on the Slave Terminal Tab Page, and
select
Clear All Memory
from the menu. You can select this menu command only when the
Safety CPU Unit is in PROGRAM mode.
The Clear All Memory for NX Unit Dialog Box is displayed.
7 Checking Operation and Actual Operation
7 - 68
NX-series Safety Control Unit User's Manual (Z930)
Summary of Contents for NX-SIH400
Page 4: ...Introduction 2 NX series Safety Control Unit User s Manual Z930 ...
Page 46: ...Revision History 44 NX series Safety Control Unit User s Manual Z930 ...
Page 108: ...2 Specifications 2 42 NX series Safety Control Unit User s Manual Z930 ...
Page 132: ...3 Installation and Wiring 3 24 NX series Safety Control Unit User s Manual Z930 ...
Page 148: ...4 Safety Control Unit Operation 4 16 NX series Safety Control Unit User s Manual Z930 ...
Page 216: ...5 System Configuration and Setup 5 44 NX series Safety Control Unit User s Manual Z930 ...
Page 306: ...6 Programming 6 90 NX series Safety Control Unit User s Manual Z930 ...
Page 390: ...8 Calculating Safety Reaction Times 8 12 NX series Safety Control Unit User s Manual Z930 ...
Page 412: ...11 Safety Data Logging 11 10 NX series Safety Control Unit User s Manual Z930 ...
Page 504: ...12 Troubleshooting 12 92 NX series Safety Control Unit User s Manual Z930 ...
Page 554: ...l I O Map Settings Appendices A 42 NX series Safety Control Unit User s Manual Z930 ...
Page 623: ...I Index I 1 NX series Safety Control Unit User s Manual Z930 I ...
Page 625: ......