Editing Connection Parameters
Use the following procedure to edit connection parameters for CIP Safety connections.
WARNING
If you select “Only Open” for the Open Type setting, make sure to verify
that the originator/target have correct configurations.
Serious injury may possibly occur due to loss of required safety func-
tions.
1
Select a connection for which the parameters need to be edited in the connection list and right-
click on it. Click
Edit
Menu.
The Connection Assignment Dialog Box is displayed.
Item
Description
I/O Assembly
I/O assemblies of the target device for which a safety connection can be
opened are listed.
Connection Type
For input connection (receiving from the target device), select either
Point to Point Connection
or
Multicast Connection
.
Open Type
Select a type for connection opening.
Configure Target Device: Perform configuration of the target device when
a connection is established. For the Safety CPU Unit, this item cannot be
selected.
Check Safety Signature: Uses the safety signature to check if the target
devices are properly configured when establishing the connection. The
safety signature consists of the Safety Configuration CRC and the Safety
Configuration Time Stamp. When the target device is the Safety CPU
Unit, this item cannot be selected.
Opening Only: Configuration check is not executed when establishing the
connection.
Expected Packet Interval (EPI)
Set an interval for communications of safety process data between the
originator and the target.
Timeout
Specify a timeout time using a multiple of the EPI value, allowed for de-
termining a communications error. The default setting is EPI x 2 [ms]
(timeout is allowed just once).
5 System Configuration and Setup
5 - 17
NX-series Safety Control Unit User's Manual (Z930)
5-4 Setting Up the Safety Process Data Communications
5
5-4-2
Setting Up the CIP Safety Communications
Summary of Contents for NX-SIH400
Page 4: ...Introduction 2 NX series Safety Control Unit User s Manual Z930 ...
Page 46: ...Revision History 44 NX series Safety Control Unit User s Manual Z930 ...
Page 108: ...2 Specifications 2 42 NX series Safety Control Unit User s Manual Z930 ...
Page 132: ...3 Installation and Wiring 3 24 NX series Safety Control Unit User s Manual Z930 ...
Page 148: ...4 Safety Control Unit Operation 4 16 NX series Safety Control Unit User s Manual Z930 ...
Page 216: ...5 System Configuration and Setup 5 44 NX series Safety Control Unit User s Manual Z930 ...
Page 306: ...6 Programming 6 90 NX series Safety Control Unit User s Manual Z930 ...
Page 390: ...8 Calculating Safety Reaction Times 8 12 NX series Safety Control Unit User s Manual Z930 ...
Page 412: ...11 Safety Data Logging 11 10 NX series Safety Control Unit User s Manual Z930 ...
Page 504: ...12 Troubleshooting 12 92 NX series Safety Control Unit User s Manual Z930 ...
Page 554: ...l I O Map Settings Appendices A 42 NX series Safety Control Unit User s Manual Z930 ...
Page 623: ...I Index I 1 NX series Safety Control Unit User s Manual Z930 I ...
Page 625: ......