Event name
Sysmac Studio Communications Connection Time-
out
Event code
951E0000 hex
Meaning
A communications timeout occurred between the Sysmac Studio and the Safety CPU Unit.
Source
Depends on where the Sysmac
Studio is connected and the sys-
tem configuration.
Source details
NX Unit
Detection tim-
ing
When applica-
ble
Error attrib-
utes
Level
Information
Recovery
---
Log category
System
Effects
User program
Continues.
Operation
If the CPU Unit was in DEBUG mode, it automati-
cally enters PROGRAM mode.
System-de-
fined varia-
bles
Variable
Data type
Name
None
None
None
Cause and
correction
Assumed cause
Correction
Prevention
The communications cable was
disconnected.
Do not do anything to disconnect
communications with the Sysmac
Studio while the Safety CPU Unit
is operating in DEBUG mode.
Perform debugging considering
the corrections that are given on
the left.
Attached in-
formation
None
Precautions/
Remarks
None
Event name
Clear All Memory Rejected
Event code
951F0000 hex
Meaning
Clearing all of memory failed.
Source
Depends on where the Sysmac
Studio is connected and the sys-
tem configuration.
Source details
NX Unit
Detection tim-
ing
When com-
manded from
user
Error attrib-
utes
Level
Information
Recovery
---
Log category
System
Effects
User program
Continues.
Operation
---
System-de-
fined varia-
bles
Variable
Data type
Name
None
None
None
Cause and
correction
Assumed cause
Correction
Prevention
The Clear All Memory operation
for a Controller or a Slave Termi-
nal was performed.
Specify the Units individually and
perform the Clear All Memory op-
eration.
Specify the Units individually and
perform the Clear All Memory op-
eration.
Attached in-
formation
Attached information 1: The Clear All Memory operation for the Controller or the Slave Terminal was per-
formed.
Precautions/
Remarks
The Clear All Memory operation for the Safety CPU Unit cannot be performed for the Controller or the
Slave Terminal.
l
User Access Log
12 Troubleshooting
12 - 67
NX-series Safety Control Unit User's Manual (Z930)
12-3 Checking for Errors with the Sysmac Studio
12
12-3-4 Error Descriptions
Summary of Contents for NX-SIH400
Page 4: ...Introduction 2 NX series Safety Control Unit User s Manual Z930 ...
Page 46: ...Revision History 44 NX series Safety Control Unit User s Manual Z930 ...
Page 108: ...2 Specifications 2 42 NX series Safety Control Unit User s Manual Z930 ...
Page 132: ...3 Installation and Wiring 3 24 NX series Safety Control Unit User s Manual Z930 ...
Page 148: ...4 Safety Control Unit Operation 4 16 NX series Safety Control Unit User s Manual Z930 ...
Page 216: ...5 System Configuration and Setup 5 44 NX series Safety Control Unit User s Manual Z930 ...
Page 306: ...6 Programming 6 90 NX series Safety Control Unit User s Manual Z930 ...
Page 390: ...8 Calculating Safety Reaction Times 8 12 NX series Safety Control Unit User s Manual Z930 ...
Page 412: ...11 Safety Data Logging 11 10 NX series Safety Control Unit User s Manual Z930 ...
Page 504: ...12 Troubleshooting 12 92 NX series Safety Control Unit User s Manual Z930 ...
Page 554: ...l I O Map Settings Appendices A 42 NX series Safety Control Unit User s Manual Z930 ...
Page 623: ...I Index I 1 NX series Safety Control Unit User s Manual Z930 I ...
Page 625: ......