3
Change the initial values of the variables.
6-8-5
Feedback Settings
You can set input status that is linked to changes in output status, such as feedback inputs for safety
relays.
Simulation must be stopped to make the feedback settings.
Use the following setting procedure.
1
Select
Simulation
–
Feedback Settings
.
The Feedback Setting Dialog Box is displayed.
Item
Description
Supported variable
types
Input
that is the destination of the feedback.
You cannot set a variable that is already set as a feedback destination.
BOOL, SAFEBOOL
Output Set the global variable
that is the source of the feedback.
BOOL, SAFEBOOL
Invert
This check box is used to invert the input value.
If you select this check box, the input value is inverted.
---
*1.
With Sysmac Studio version 1.11, you can use device variables and exposed variables only.
*2.
With Sysmac Studio version 1.11, set variables with the same variable type for both the source and
destination.
With Sysmac Studio version 1.12 and later, you can set different variable types for the source and
destination.
2
Press the
Insert
Key in the feedback setting table, or right-click in the feedback setting table
and select
Create New
from the menu.
Cells are added for new settings.
You can set up to 128 sets of feedback settings.
6 Programming
6 - 83
NX-series Safety Control Unit User's Manual (Z930)
6-8
Offline Debugging
6
6-8-5
Feedback Settings
Summary of Contents for NX-SIH400
Page 4: ...Introduction 2 NX series Safety Control Unit User s Manual Z930 ...
Page 46: ...Revision History 44 NX series Safety Control Unit User s Manual Z930 ...
Page 108: ...2 Specifications 2 42 NX series Safety Control Unit User s Manual Z930 ...
Page 132: ...3 Installation and Wiring 3 24 NX series Safety Control Unit User s Manual Z930 ...
Page 148: ...4 Safety Control Unit Operation 4 16 NX series Safety Control Unit User s Manual Z930 ...
Page 216: ...5 System Configuration and Setup 5 44 NX series Safety Control Unit User s Manual Z930 ...
Page 306: ...6 Programming 6 90 NX series Safety Control Unit User s Manual Z930 ...
Page 390: ...8 Calculating Safety Reaction Times 8 12 NX series Safety Control Unit User s Manual Z930 ...
Page 412: ...11 Safety Data Logging 11 10 NX series Safety Control Unit User s Manual Z930 ...
Page 504: ...12 Troubleshooting 12 92 NX series Safety Control Unit User s Manual Z930 ...
Page 554: ...l I O Map Settings Appendices A 42 NX series Safety Control Unit User s Manual Z930 ...
Page 623: ...I Index I 1 NX series Safety Control Unit User s Manual Z930 I ...
Page 625: ......