Event name
CIP Safety Target Connection Timeout
Event code
80340000 hex
Meaning
A timeout occurred in the CIP Safety Target connection.
Source
Depends on where the Sysmac
Studio is connected and the sys-
tem configuration.
Source details
NX Unit
Detection tim-
ing
In DEBUG
mode (STOP-
PED), DEBUG
mode (RUN),
or RUN mode
Error attrib-
utes
Level
Minor fault
Recovery
Automatic re-
covery when
cause of error
is removed
Log category
System
Effects
User program
Continues.
Operation
The Unit continues to operate, but the safe states
are used for the I/O data of the safety connection
where the error was detected.
System-de-
fined varia-
bles
Variable
Data type
Name
None
None
None
Cause and
correction
Assumed cause
Correction
Prevention
The communications cable is dis-
connected or broken.
Connect the communication ca-
ble securely.
Set the system configuration and
setup according to the correc-
tions that are given on the left.
The originator device entered a
state where it could not accept
the connection.
Check if the originator device is
in a state where it can accept the
connection.
The timeout value in the commu-
nications setup is too small.
Increase the timeout value in the
communications setup and trans-
fer the settings.
There is excessive noise.
Implement noise countermeas-
ures.
Attached in-
formation
Attached infor-
mation 1:
Assembly Instance No.
0300 hex: Input Assembly 1
0301 hex: Input Assembly 2
0302 hex: Input Assembly 3
03A0 hex: Output Assembly 1
Precautions/
Remarks
None
12 Troubleshooting
12 - 42
NX-series Safety Control Unit User's Manual (Z930)
Summary of Contents for NX-SIH400
Page 4: ...Introduction 2 NX series Safety Control Unit User s Manual Z930 ...
Page 46: ...Revision History 44 NX series Safety Control Unit User s Manual Z930 ...
Page 108: ...2 Specifications 2 42 NX series Safety Control Unit User s Manual Z930 ...
Page 132: ...3 Installation and Wiring 3 24 NX series Safety Control Unit User s Manual Z930 ...
Page 148: ...4 Safety Control Unit Operation 4 16 NX series Safety Control Unit User s Manual Z930 ...
Page 216: ...5 System Configuration and Setup 5 44 NX series Safety Control Unit User s Manual Z930 ...
Page 306: ...6 Programming 6 90 NX series Safety Control Unit User s Manual Z930 ...
Page 390: ...8 Calculating Safety Reaction Times 8 12 NX series Safety Control Unit User s Manual Z930 ...
Page 412: ...11 Safety Data Logging 11 10 NX series Safety Control Unit User s Manual Z930 ...
Page 504: ...12 Troubleshooting 12 92 NX series Safety Control Unit User s Manual Z930 ...
Page 554: ...l I O Map Settings Appendices A 42 NX series Safety Control Unit User s Manual Z930 ...
Page 623: ...I Index I 1 NX series Safety Control Unit User s Manual Z930 I ...