Event name
NX Bus Communications Settings Read Error
Event code
10500000 hex
Meaning
There is an error in the NX Bus communications settings that are saved in non-volatile memory.
Source
Depends on where the Sysmac
Studio is connected and the sys-
tem configuration.
Source details
NX Unit
Detection tim-
ing
At power ON or
restart
Error attrib-
utes
Level
Minor fault
Recovery
When settings
are transferred
Log category
System
Effects
User program
Continues.
Operation
I/O refreshing stops for the CPU Unit.
System-de-
fined varia-
bles
Variable
Data type
Name
None
None
None
Cause and
correction
Assumed cause
Correction
Prevention
A hardware failure occurred in
the non-volatile memory.
Transfer the configuration infor-
mation to the Safety CPU Unit
again. Replace the CPU Unit if
the error occurs again.
None
Power was turned OFF while
saving data to the non-volatile
memory.
Do not turn OFF the power sup-
ply while transferring parameters
from the Sysmac Studio.
Attached in-
formation
None
Precautions/
Remarks
None
Event name
Safety Application Data Read Error
Event code
10510000 hex
Meaning
There is an error in the safety application data that is saved in non-volatile memory.
Source
Depends on where the Sysmac
Studio is connected and the sys-
tem configuration.
Source details
NX Unit
Detection tim-
ing
At power ON or
restart
Error attrib-
utes
Level
Minor fault
Recovery
When settings
are transferred
Log category
System
Effects
User program
Continues.
Operation
The safety program is not executed in the Safety
CPU Unit and it operates in PROGRAM mode.
System-de-
fined varia-
bles
Variable
Data type
Name
None
None
None
Cause and
correction
Assumed cause
Correction
Prevention
A hardware failure occurred in
the non-volatile memory.
Transfer the safety application
data to the Safety CPU Unit
again.
None
Power was turned OFF while
saving data to the non-volatile
memory.
Do not turn OFF the power sup-
ply while transferring parameters
from the Sysmac Studio.
Attached in-
formation
None
Precautions/
Remarks
None
12 Troubleshooting
12 - 56
NX-series Safety Control Unit User's Manual (Z930)
Summary of Contents for NX-SIH400
Page 4: ...Introduction 2 NX series Safety Control Unit User s Manual Z930 ...
Page 46: ...Revision History 44 NX series Safety Control Unit User s Manual Z930 ...
Page 108: ...2 Specifications 2 42 NX series Safety Control Unit User s Manual Z930 ...
Page 132: ...3 Installation and Wiring 3 24 NX series Safety Control Unit User s Manual Z930 ...
Page 148: ...4 Safety Control Unit Operation 4 16 NX series Safety Control Unit User s Manual Z930 ...
Page 216: ...5 System Configuration and Setup 5 44 NX series Safety Control Unit User s Manual Z930 ...
Page 306: ...6 Programming 6 90 NX series Safety Control Unit User s Manual Z930 ...
Page 390: ...8 Calculating Safety Reaction Times 8 12 NX series Safety Control Unit User s Manual Z930 ...
Page 412: ...11 Safety Data Logging 11 10 NX series Safety Control Unit User s Manual Z930 ...
Page 504: ...12 Troubleshooting 12 92 NX series Safety Control Unit User s Manual Z930 ...
Page 554: ...l I O Map Settings Appendices A 42 NX series Safety Control Unit User s Manual Z930 ...
Page 623: ...I Index I 1 NX series Safety Control Unit User s Manual Z930 I ...
Page 625: ......