Event code
Event name
Meaning
Assumed cause
Level
Reference
M
a
j
P
rt
M
i
n
O
b
s
I
n
f
o
80200000 hex
NX Unit I/O
Communica-
tions Error
An I/O communica-
tions error occurred
between the NX bus
master and the NX
Unit.
•
The NX Unit is not mounted
properly.
•
The power cable for the Unit
power supply is disconnected.
Or, the wiring from the Unit
power supply to the NX Units
is incorrect.
•
The power cable for the Unit
power supply is broken.
•
The unit power voltage is out
of the supported range, or the
unit power capacity is not suffi-
cient.
•
There is a hardware error in
the NX Unit.
¡
80300000 hex
Safety Proc-
ess Data
Communica-
tions Time-
out
A communications
timeout occurred in
safety process data
communications with
the Safety Control
Unit.
•
A setting is not correct. The
setting of the safety task peri-
od is too short.
•
There is excessive noise.
•
The Safety CPU Unit or safety
slave entered a status where it
could not continue safety proc-
ess data communications.
•
The process data communica-
tions were not performed cor-
rectly because an error or sta-
tus change occurred in the NX
bus master to which the Unit is
connected.
¡
84F10000 hex
NX Bus I/O
Communica-
tions Stop-
ped
An error occurred in
I/O communications
between the NX bus
master and an NX
Unit.
There is a hardware error in the
NX bus master or an NX Unit.
¡
l
Safety I/O Errors
Event code
Event name
Meaning
Assumed cause
Level
Reference
M
a
j
P
rt
M
i
n
O
b
s
I
n
f
o
05210000 hex
Internal Cir-
cuit Error at
Safety Input
A fault was detected
in the internal circuit
for the safety input
terminal.
•
The internal circuit for the safe-
ty input terminal is faulty.
•
A memory error or signal error
occurred due to a transient
cause, such as an excessive
noise.
¡
12 Troubleshooting
12 - 28
NX-series Safety Control Unit User's Manual (Z930)
Summary of Contents for NX-SIH400
Page 4: ...Introduction 2 NX series Safety Control Unit User s Manual Z930 ...
Page 46: ...Revision History 44 NX series Safety Control Unit User s Manual Z930 ...
Page 108: ...2 Specifications 2 42 NX series Safety Control Unit User s Manual Z930 ...
Page 132: ...3 Installation and Wiring 3 24 NX series Safety Control Unit User s Manual Z930 ...
Page 148: ...4 Safety Control Unit Operation 4 16 NX series Safety Control Unit User s Manual Z930 ...
Page 216: ...5 System Configuration and Setup 5 44 NX series Safety Control Unit User s Manual Z930 ...
Page 306: ...6 Programming 6 90 NX series Safety Control Unit User s Manual Z930 ...
Page 390: ...8 Calculating Safety Reaction Times 8 12 NX series Safety Control Unit User s Manual Z930 ...
Page 412: ...11 Safety Data Logging 11 10 NX series Safety Control Unit User s Manual Z930 ...
Page 504: ...12 Troubleshooting 12 92 NX series Safety Control Unit User s Manual Z930 ...
Page 554: ...l I O Map Settings Appendices A 42 NX series Safety Control Unit User s Manual Z930 ...
Page 623: ...I Index I 1 NX series Safety Control Unit User s Manual Z930 I ...
Page 625: ......