8-3
FSoE Watchdog Timer
This section describes the FSoE watchdog timers.
8-3-1
FSoE Watchdog Timers
An FSoE watchdog timer is used for timeouts in safety process data between the Safety CPU Unit and
Safety I/O Units.
The FSoE watchdog timers affect the safety reaction times.
You can increase the settings of the FSoE watchdog timers to help prevent timeouts in safety process
data communications. Set this time as required.
To increase the communications timeout time, you must change both the value of the FSoE watchdog
timer and the safety task period. Refer to
8-2-4 Setting the Safety Task Period
mation on setting the safety task period.
8-3-2
Checking FSoE Watchdog Timers
Use the following procedure to check the FSoE watchdog timers.
1
In the Multiview Explorer, select the target Safety CPU Unit in the Controller Selection Box.
2
Double-click
Safety I/O
under
Configurations and Setup
−
Communications
−
Safety
.
The following Safety I/O Unit Setting Tab Page is displayed.
The values of the FSoE watchdog timers are displayed in the
FSoE Watchdog Timer
Column
for the Safety I/O Units.
Precautions for Correct Use
If you use NX-SL
££££
version 1.1 and Free-Run refreshing is set in even one communica-
tions setup of the EtherCAT Slave Terminals to which the Safety Control Units are connected,
you must change the FSoE watchdog timer.
Set the FSoE watchdog timer to at least the sum of the
FSoE Watchdog Timer
displayed by
the Sysmac Studio and the value of the following correction.
• When EtherCAT Communications Cycle Is Greater Than 1.9 ms
Correction =
EtherCAT communications cycle
• When EtherCAT Communications Cycle Is 1.9 ms or Lower
Correction = 3.8ms -
EtherCAT communications cycle
8 Calculating Safety Reaction Times
8 - 9
NX-series Safety Control Unit User's Manual (Z930)
8-3 FSoE W
atchdog T
imer
8
8-3-1
FSoE W
atchdog T
imers
Summary of Contents for NX-SIH400
Page 4: ...Introduction 2 NX series Safety Control Unit User s Manual Z930 ...
Page 46: ...Revision History 44 NX series Safety Control Unit User s Manual Z930 ...
Page 108: ...2 Specifications 2 42 NX series Safety Control Unit User s Manual Z930 ...
Page 132: ...3 Installation and Wiring 3 24 NX series Safety Control Unit User s Manual Z930 ...
Page 148: ...4 Safety Control Unit Operation 4 16 NX series Safety Control Unit User s Manual Z930 ...
Page 216: ...5 System Configuration and Setup 5 44 NX series Safety Control Unit User s Manual Z930 ...
Page 306: ...6 Programming 6 90 NX series Safety Control Unit User s Manual Z930 ...
Page 390: ...8 Calculating Safety Reaction Times 8 12 NX series Safety Control Unit User s Manual Z930 ...
Page 412: ...11 Safety Data Logging 11 10 NX series Safety Control Unit User s Manual Z930 ...
Page 504: ...12 Troubleshooting 12 92 NX series Safety Control Unit User s Manual Z930 ...
Page 554: ...l I O Map Settings Appendices A 42 NX series Safety Control Unit User s Manual Z930 ...
Page 623: ...I Index I 1 NX series Safety Control Unit User s Manual Z930 I ...
Page 625: ......