Item
Specification
Operating environment Ambient operating tem-
perature
0 to 55°C
Ambient operating humid-
ity
10% to 95% (with no condensation or icing)
Atmosphere
Must be free from corrosive gases.
Ambient storage tempera-
ture
−25 to 70°C (with no condensation or icing)
Altitude
2,000 m max.
Pollution degree
Pollution degree 2 or less: Conforms to JIS B 3502
and IEC 61131-2
Noise immunity
Conforms to IEC 61131-2, 2 kV (power supply line)
Insulation class
CLASS III (SELV)
Overvoltage category
Category II: Conforms to JIS B 3502 and IEC 61131-2
EMC immunity level
Zone B
Vibration resistance
Conforms to IEC 60068-2-6
5 to 8.4 Hz with amplitude of 3.5 mm
8.4 to 150 Hz, acceleration of 9.8 m/s
2
100 min. in each X, Y, and Z directions (10 sweeps of
10 min. each = 100 min. total)
Shock resistance
Conforms to IEC 60068-2-27
147 m/s
2
, 3 times in each X, Y, and Z directions
Isolation method
Photocoupler isolation
Insulation resistance
20 MΩ between isolated circuits (at 100 VDC)
Dielectric strength
510 VAC between isolated circuits for 1 minute at a
leakage current of 5 mA max.
Installation method
DIN Track (IEC 60715 TH35-7.5/TH35-15)
Individual Specifications
This section provides the individual specifications of the Safety Input Unit.
l
Datasheet Items for Safety Input Unit
The following table gives the meaning of the datasheet items for the Safety Input Units.
Item
Specification
Number of safety input points
This is the number of safety input points on the Unit.
Number of test output points
This is the number of test output points on the Unit. The test output points
are used with the safety input terminals.
Internal I/O common
This is the polarity that the Unit uses to connect to input devices.
Rated input voltage
This is the rated input voltage of the Unit.
OMRON Special Safety Input De-
vices
This tells whether the Unit supports the connection of OMRON Special
Safety Input Devices (D40A Non-contact Door Switches, E3FS Single
Beam Safety Sensors, etc.).
Number of safety slave connec-
tions
This is the number of slave connections that the Unit can have through
FSoE. You can perform communications with one FSoE master device per
connection.
I/O refreshing method
This is the I/O refreshing method for the Unit.
2 Specifications
2 - 17
NX-series Safety Control Unit User's Manual (Z930)
2-2
Safety Input Unit
2
2-2-1
Models and Specifications
Summary of Contents for NX-SIH400
Page 4: ...Introduction 2 NX series Safety Control Unit User s Manual Z930 ...
Page 46: ...Revision History 44 NX series Safety Control Unit User s Manual Z930 ...
Page 108: ...2 Specifications 2 42 NX series Safety Control Unit User s Manual Z930 ...
Page 132: ...3 Installation and Wiring 3 24 NX series Safety Control Unit User s Manual Z930 ...
Page 148: ...4 Safety Control Unit Operation 4 16 NX series Safety Control Unit User s Manual Z930 ...
Page 216: ...5 System Configuration and Setup 5 44 NX series Safety Control Unit User s Manual Z930 ...
Page 306: ...6 Programming 6 90 NX series Safety Control Unit User s Manual Z930 ...
Page 390: ...8 Calculating Safety Reaction Times 8 12 NX series Safety Control Unit User s Manual Z930 ...
Page 412: ...11 Safety Data Logging 11 10 NX series Safety Control Unit User s Manual Z930 ...
Page 504: ...12 Troubleshooting 12 92 NX series Safety Control Unit User s Manual Z930 ...
Page 554: ...l I O Map Settings Appendices A 42 NX series Safety Control Unit User s Manual Z930 ...
Page 623: ...I Index I 1 NX series Safety Control Unit User s Manual Z930 I ...
Page 625: ......