EtherNet/IP Connection Status Codes
and Troubleshooting
This section describes how to identify the cause of an error by the connection status of the tag data
link and how to troubleshoot the error when the originator is an NJ/NX-series CPU Unit. The connec-
tion status can be monitored by the device monitor function of the Network Configurator. Refer to the
NJ/NX-series CPU Unit Built-in EtherNet/IP Port User’s Manual (Cat. No. W506)
for details of how to
start Network Configurator and the device monitor function.
Connection sta-
tus
Error cause
Corrective action example
Gener-
al Sta-
tus
(hex)
Addi-
tional
Status
(hex)
00
0000
Normal status
code
The connection has been
opened and the tag data link
is communicating normally.
-
01
0106
Duplicate consum-
ers
Attempted to open multiple
connections for single-con-
sumer data.
If you change the scanner while a tag data link
is established, restart the PMAC.
01
0112
Error code re-
turned from target
The RPI value is invalid.
If a single connection is connected to multiple
originators, check if the RPI values are not dif-
ferent.
01
0114
Error code re-
turned from target
The Vendor ID and Product
Code did not match when the
connection was opened.
Check if the originator did not specify a target
device model that was different from the model
of the target device actually connected.
01
0115
Error code re-
turned from target
The Device Type did not
match when opening connec-
tion.
Check if the originator did not specify a target
device model that was different from the model
of the target device actually connected.
01
0116
Error code re-
turned from target
The Major/Minor Revisions did
not match when opening con-
nection.
Check if the revision in the EDS file in use
matches the revision of the device.
01
0117
Error code re-
turned from target
The tag set specified in the
connection’s target variables
does not exist.
Check that the tag settings are correct with the
EtherNet/IP setting tool.
01
011A
Error code re-
turned from target
The number of connections is
more than 32.
Does not occur.
01
0127
Error code re-
turned from target
The connection size is differ-
ent between the originator and
target.
Check if the connection size of the target
matches the connection size of the originator.
01
0128
01
012F
Error code re-
turned from target
The application path is differ-
ent between the originator and
target.
Check that the setting values for the target vari-
able and originator variable are correct with the
EtherNet/IP setting tool.
6 Troubleshooting
6-20
CK3M-series Programmable Multi-Axis Controller User's Manual Hardware (O036)
Summary of Contents for CK3M Series
Page 6: ...Manual Structure 4 CK3M series Programmable Multi Axis Controller User s Manual Hardware O036...
Page 284: ...Appendices A 42 CK3M series Programmable Multi Axis Controller User s Manual Hardware O036...
Page 285: ...I Index I 1 CK3M series Programmable Multi Axis Controller User s Manual Hardware O036 I...
Page 287: ......