![Omron CK3M Series Hardware User Manual Download Page 235](http://html1.mh-extra.com/html/omron/ck3m-series/ck3m-series_hardware-user-manual_742506235.webp)
Connection sta-
tus
Error cause
Corrective action example
Gener-
al Sta-
tus
(hex)
Addi-
tional
Status
(hex)
01
0203
Error code gener-
ated by originator
The connection timed out.
Timeout of tag data link communication from
the target occurred. Check the power supply to
and cable wiring of the devices on the path in-
cluding the target and switch. If the cause is a
decrease in performance due to heavy load, re-
view the performance design by increasing the
timeout value, RPI, or etc.
01
0204
Error code gener-
ated by originator
The connection open process
timed out.
The target did not respond. Check the power
supply to and cable wiring of the devices on the
path including the target and switch.
01
0302
Error code gener-
ated by originator
or returned from
target
The total pps of the entire
EtherNet/IP settings is more
than 3,200.
Review the EtherNet/IP settings so that pps
does not exceed the limit.
*1.
If the number of connections is more than 32,
Tag Data Link Timeout
will occur repeatedly. If the controller log contains
repetitive
Tag Data Link Timeout
records, check if the number of connections is appropriate.
6 Troubleshooting
6-21
CK3M-series Programmable Multi-Axis Controller User's Manual Hardware (O036)
6-5
EtherNet/IP Connection Status Codes and T
roubleshooting
6
Summary of Contents for CK3M Series
Page 6: ...Manual Structure 4 CK3M series Programmable Multi Axis Controller User s Manual Hardware O036...
Page 284: ...Appendices A 42 CK3M series Programmable Multi Axis Controller User s Manual Hardware O036...
Page 285: ...I Index I 1 CK3M series Programmable Multi Axis Controller User s Manual Hardware O036 I...
Page 287: ......