![Omron CK3M Series Hardware User Manual Download Page 86](http://html1.mh-extra.com/html/omron/ck3m-series/ck3m-series_hardware-user-manual_742506086.webp)
Connection diagram
NPN type
24 VDC
V1
IN00
IN01
IN15
PNP type
24 VDC
IN00
IN01
IN15
G1
General digital
output (NPN)
Internal common
NPN
Rated voltage
12 to 24 VDC
Current consumption
40 mA max.
Operating load voltage
range
10.2 to 26.4 VDC
Maximum load current
0.5 A/point, 2 A/Unit
Maximum inrush current
4.0 A/point, 10 ms max.
Leakage current
0.1 mA max.
Residual voltage
1.0 V max.
ON/OFF response time
0.1 ms max./0.8 ms max.
Isolation method
Isolation by Photocoupler (between output and internal cir-
cuit)
Load short-circuit preven-
tion
Not provided