![Omron CK3M Series Hardware User Manual Download Page 99](http://html1.mh-extra.com/html/omron/ck3m-series/ck3m-series_hardware-user-manual_742506099.webp)
For single-ended input
FG
FG
Input 0- to 7-
AGND
Input 0+ to 7+
•
If any of Input 0- to Input 7- is single ended input, apply a
short-circuit between the input and AGND.
•
Use a shielded cable and ground at both ends of the ca-
ble.
Power consumption
CK3W-AD3100: 5 V 0.9 W max., 24 V 2.0 W max.
CK3W-AD2100: 5 V 0.9 W max., 24 V 1.4 W max.
Dimensions (height × depth × width)
90(H)/80(D)/31.6(W)
Weight
CK3W-AD3100: 140 g max.
CK3W-AD2100: 120 g max.
*1.
Differential input and single-ended input can be mixed in a Unit.
3-5-2
Part Names and Functions
(A)
(F)
(B)
(C)
(D)
(E)
Letter
Name
Function
A
Slider
Holds the Units together.
B
Power supply status indicator Shows the power supply status.
C
Terminal block
Connects the analog input.
D
Unit connector
Connector that connects to the Unit.
E
DIN Track mounting hook
Used to mount the Unit to a DIN Track.
F
Address switch
Sets the Gate3 Index.
3 Configuration Units
3-55
CK3M-series Programmable Multi-Axis Controller User's Manual Hardware (O036)
3-5
Analog Input Unit
3
3-5-2
Part Names and Functions