Description
Cause
Corrective action
Hardware watchdog
timer error
Unit disconnection
during operations
Make sure that the Units are connected correctly.
Illegal user program
6-3-3 Initialization of CPU Unit Using USB Memory
page 6-9, and execute re-initialization.
Ingress of conductive
object
If there is conductive material nearby, blow air through the CPU
Unit.
Noise
If the error did not result from the above causes, cycle the power
to the Controller and see if that resets the error. If the error oc-
curs frequently, check the FG and power supply lines to see if
noise is entering on them. Implement noise countermeasures as
required.
CPU Unit failure
If the error persists even after you make the above corrections,
replace the CPU Unit.
Initial process error
Ingress of conductive
object
If there is conductive material nearby, blow air through the CPU
Unit.
Noise
If the error did not result from the above causes, cycle the power
to the Controller and see if that resets the error. If the error oc-
curs frequently, check noise entry paths such as the FG and the
power supply lines and implement noise countermeasures as re-
quired.
CPU Unit failure
If the error persists even after you make the above corrections,
replace the CPU Unit.
6-3-2
Non-fatal Errors in the CPU Unit
For non-fatal errors in the CPU Unit, take the following corrective actions depending on the nature of
the error.
Description
Cause
Corrective action
EtherCAT physical layer
link not established
The Ethernet cable used for
EtherCAT communications is
broken or the specified cable is
not being used.
If the Ethernet cable is broken or if the specified
cable is not being used, replace the cable.
Disconnected connector on the
Ethernet cable used for Ether-
CAT communications, contact
failure, or part failure
Reconnect the connector and check to ensure it is
mated correctly.
Power is not supplied to the
first slave connected to the
CPU Unit.
Supply power to the slave.
Failure of slave within Ether-
CAT network configuration
Replace the slave.
Noise
Check noise entry paths, and implement noise-re-
lated countermeasures as required.
CPU Unit failure
Replace the CPU Unit.
6 Troubleshooting
6-6
CK3M-series Programmable Multi-Axis Controller User's Manual Hardware (O036)