![Omron CK3M Series Hardware User Manual Download Page 92](http://html1.mh-extra.com/html/omron/ck3m-series/ck3m-series_hardware-user-manual_742506092.webp)
Connection diagram
12 to 24 VDC
V2
OUT00
OUT01
OUT15
G2
L
L
L
Digital output
(PNP)
Internal common
PNP
Rated voltage
12 to 24 VDC
Current consumption
80 mA max.
Operating load voltage
range
10.2 to 26.4 VDC
Maximum load current
0.5 A/point, 2 A/Unit
Maximum inrush current
4.0 A/point, 10 ms max.
Leakage current
0.1 mA max.
Residual voltage
1.0 V max.
ON/OFF response time
0.1 ms max./0.8 ms max.
Isolation method
Isolation by Photocoupler (between output and internal cir-
cuit)
Load short-circuit preven-
tion
Provided
Circuit configuration
Internal
circuit
V2
G2
OUT00
OUT01
OUT15
Short-circuit
protection
Short-circuit
protection
Short-circuit
protection
3 Configuration Units
3-48