![Omron CK3M Series Hardware User Manual Download Page 52](http://html1.mh-extra.com/html/omron/ck3m-series/ck3m-series_hardware-user-manual_742506052.webp)
Terminal Arrangement
Terminal block
Abbreviation Signal name
+
-
WDTOUT-
Output Status
In normal operation, it is ON, and at other times it is OFF.
Status
Output
When unit power is OFF
OFF
During normal operation
ON
When hardware watchdog error occurs OFF
When software watchdog error occurs
OFF
Output Specifications
Item
Specification
Rated voltage
24 VDC
Operating load voltage range
20.4 to 26.4 VDC
Maximum load current
0.1 A
Leakage current
0.1 mA max.
Residual voltage
1.5 V max.
ON/OFF response time
10 ms max./10 ms max.
Isolation method
Photocoupler isolation
Circuit configuration
WDTOUT-
Internal
circuit
3 Configuration Units
3-8
CK3M-series Programmable Multi-Axis Controller User's Manual Hardware (O036)
Summary of Contents for CK3M Series
Page 6: ...Manual Structure 4 CK3M series Programmable Multi Axis Controller User s Manual Hardware O036...
Page 284: ...Appendices A 42 CK3M series Programmable Multi Axis Controller User s Manual Hardware O036...
Page 285: ...I Index I 1 CK3M series Programmable Multi Axis Controller User s Manual Hardware O036 I...
Page 287: ......