7 Settings
PCS-9611 Feeder Relay
7-1
Date: 2014-04-08
7.1 Overview
The settings are used to determine the characteristic of each protective element and operation
mode of the relay. It is necessary to configure the settings of this relay according to engineering
demands before putting this relay into service. If the settings are not configured correctly, this
relay maybe works abnormally (such as communication interruption, printing out unexpected
codes etc.), it also can lead to much more serious accident (such as unwanted operation, missing
operation) sometimes.
The settings of this relay include system settings, protection settings, communication settings and
miscellaneous settings. The user can configure these settings or parameters manually (see
Section 8.2.6.2
). Remote modification is also supported (IEC61850, IEC60870-5-103 or DNP3.0
interface, see
Chapter 10
for the details about these protocols).
NOTE!
If a CPU module is replaced, it is necessary to configure all the settings again
according to the configuration of the CPU module which is replaced.
7.2 System Settings
The system settings (in the submenu
“
System Settings
”) are mainly used to set the rated value
of VT and CT.
The following table lists all the system parameters.
No.
Menu text
Explanation
Range
Step
1
Acti ve_Grp
The active setting group number
1 ~ 10
1
2
Opt_SysFreq
Select the rated system frequency:
“0”, 50Hz; “1”, 60Hz
0~1
1
3
PrimaryEquip_Name
The name of the protected primary equipment
1~7 characters
4
Prot.I1n
Rated primary value of protection phase CT
0~20000A
1A
5
Prot.I2n
Rated secondary value of protection phase CT
1/5A
4A
6
Measmt.I1n
Rated primary value of metering phase CT
0~20000A
1A
7
Measmt.I2n
Rated secondary value of metering phase CT
1/5A
4A
8
Neu1.I1n
Rated primary value of the No.1 zero sequence CT
0~20000A
1A
9
Neu1.I2n
Rated secondary value of the No.1 zero sequence CT
1/5A
4A
10
Neu2.I1n
Rated primary value of the No.2 zero sequence CT
0~20000A
1A
11
Neu2.I2n
Rated secondary value of the No.2 zero sequence CT
1/5A
4A
12
SEF.I1n
Rated primary value of sensitive zero sequence CT
0~20000A
1A
13
SEF.I2n
Rated secondary value of sensitive zero sequence CT
1/5A
4A
14
Prot.U1n
Rated primary value of protection VT
0.1~500.0kV
0.001kV
15
Prot.U2n
Rated secondary value of protection VT
100~200V
0.001V
16
Syn.U1n
Rated primary value of synchro-check VT
0.1~500.0kV
0.001kV
17
Syn.U2n
Rated secondary value of synchro-check VT
10~200V
0.001V
18
Delt.U1n
Rated primary value of zero sequence VT
0.1~500.0kV
0.001kV
Summary of Contents for PCS-9611
Page 1: ...PCS 9611 Feeder Relay Instruction Manual NR Electric Co Ltd...
Page 2: ......
Page 10: ...1 Introduction PCS 9611 Feeder Relay 1 b Date 2014 04 08...
Page 30: ...2 Technical Data PCS 9611 Feeder Relay 2 14 Date 2014 04 08...
Page 36: ...3 Operation Theory PCS 9611 Feeder Relay 3 f Date 2014 04 08...
Page 108: ...4 Supervision PCS 9611 Feeder Relay 4 b Date 2014 04 08...
Page 116: ...5 Management Function PCS 9611 Feeder Relay 5 b Date 2014 04 08...
Page 120: ...5 Management Function PCS 9611 Feeder Relay 5 4 Date 2014 04 08...
Page 218: ...9 Configurable Function PCS 9611 Feeder Relay 9 b Date 2014 04 08...
Page 232: ...9 Configurable Function PCS 9611 Feeder Relay 9 14 Date 2014 04 08...
Page 262: ...11 Installation PCS 9611 Feeder Relay 11 b Date 2014 04 08...
Page 272: ...12 Commissioning PCS 9611 Feeder Relay 12 b Date 2014 04 08...
Page 292: ...13 Maintenance PCS 9611 Feeder Relay 13 b Date 2014 04 08...
Page 296: ...14 Decommissioning and Disposal PCS 9611 Feeder Relay 14 b Date 2014 04 08...
Page 298: ...14 Decommissioning and Disposal PCS 9611 Feeder Relay 14 2 Date 2014 04 08...
Page 300: ...15 Manual Version History PCS 9611 Feeder Relay 15 2 Date 2014 04 08...