7 Settings
PCS-9611 Feeder Relay
7-13
Date: 2014-04-08
13
50/51SEF3.3I0_Set
The current setting of the stage 3 sensitive earth
fault protection
0.005~1.0A
0.001A
14
50/51SEF3.t_Op
The time setting of the stage 3 sensitive earth
fault protection
0~100s
0.001s
15
50/51SEF3.Opt_Dir
The setting is used to select the directional mode
for the stage 3 SEF protection, see
Section 3.6.3
0~2
1
16
50/51SEF3.En
The logic setting of the stage 3 sensitive earth
fault protection
0~1
1
17
50/51SEF3.OutMap
The output matrix setting of the stage 3 sensitive
earth fault protection
0x00000 ~
0xFFFFF
1
18
50/51SEF4.3I0_Set
The current setting of the stage 4 sensitive earth
fault protection
0.005~1.0A
0.001A
19
50/51SEF4.t_Op
The time setting of the stage 4 sensitive earth
fault protection
0~100s
0.001s
20
50/51SEF4.Opt_Dir
The setting is used to select the directional mode
for the stage 4 SEF protection, see
Section 3.6.3
0~2
1
21
50/51SEF4.En
The logic setting of the stage 4 sensitive earth
fault protection
0~1
1
22
50/51SEF4.OutMap
The output matrix setting of the stage 4 sensitive
earth fault protection
0x00000 ~
0xFFFFF
1
23
50/51SEF4.Opt_Curve
The setting is for selecting the inverse time
characteristic curve for SEF4 protection
0~13
1
24
50/51SEF4.TMS
The time multiplier setting of the IDMT sensitive
earth fault protection
0.05~100.0
0.001
25
50/51SEF4.tmin
The minimum operation time setting of the IDMT
sensitive earth fault protection
0~100s
0.001s
26
50/51SEF4.K
Constant
“k” for the IDMT sensitive earth fault
protection, see
Section 3.6.2
0.001~120.0
0.0001
27
50/51SEF4.C
Constant
“C” for the IDMT sensitive earth fault
protection, see
Section 3.6.2
0.00~1.00
0.0001
28
50/51SEF4.Alpha
Constant
“α” for the IDMT sensitive earth fault
protection, see
Section 3.6.2
0.01~3.00
0.0001
NOTE!
1. The setting [50/51SEFx.Opt_Dir] (x: 1~4) is used to select the directional mode for the stage
x (x: 1~4) sensitive earth fault protection respectively.
“0” is the non-directional mode; “1” is
the forward directional mode; and
“2” is the reverse directional mode.
7.3.5 Breaker Failure Protection Settings
The breaker failure protection settings (in the submenu
“
BFP Settings
”) are used to determine the
characteristic of the breaker failure protection.
All the settings of the breaker failure protection are listed in the following table.
Summary of Contents for PCS-9611
Page 1: ...PCS 9611 Feeder Relay Instruction Manual NR Electric Co Ltd...
Page 2: ......
Page 10: ...1 Introduction PCS 9611 Feeder Relay 1 b Date 2014 04 08...
Page 30: ...2 Technical Data PCS 9611 Feeder Relay 2 14 Date 2014 04 08...
Page 36: ...3 Operation Theory PCS 9611 Feeder Relay 3 f Date 2014 04 08...
Page 108: ...4 Supervision PCS 9611 Feeder Relay 4 b Date 2014 04 08...
Page 116: ...5 Management Function PCS 9611 Feeder Relay 5 b Date 2014 04 08...
Page 120: ...5 Management Function PCS 9611 Feeder Relay 5 4 Date 2014 04 08...
Page 218: ...9 Configurable Function PCS 9611 Feeder Relay 9 b Date 2014 04 08...
Page 232: ...9 Configurable Function PCS 9611 Feeder Relay 9 14 Date 2014 04 08...
Page 262: ...11 Installation PCS 9611 Feeder Relay 11 b Date 2014 04 08...
Page 272: ...12 Commissioning PCS 9611 Feeder Relay 12 b Date 2014 04 08...
Page 292: ...13 Maintenance PCS 9611 Feeder Relay 13 b Date 2014 04 08...
Page 296: ...14 Decommissioning and Disposal PCS 9611 Feeder Relay 14 b Date 2014 04 08...
Page 298: ...14 Decommissioning and Disposal PCS 9611 Feeder Relay 14 2 Date 2014 04 08...
Page 300: ...15 Manual Version History PCS 9611 Feeder Relay 15 2 Date 2014 04 08...