3 Operation Theory
PCS-9611 Feeder Relay
3-63
Date: 2014-04-08
8
25A.f_Diff
The
frequency
difference setting
of
the
auto-closing synchronism check function
0~2Hz
0.001Hz
9
25A.phi_Diff
The phase angle difference setting of the
auto-closing synchronism check function
0~60°
1°
10
25A.t_Wait
The waiting time setting of the auto-closing
synchronism check function
0.01~60s
0.001s
11
25A.Opt_DdChk
The setting for selecting the dead check mode of
the auto-closing synchronism check function
1~7
1
12
25A.t_DdChk
The time setting of the dead check function of the
auto-closer
0.01~25s
0.001s
13
25A.t_SynChk
The time setting of the synchronism check
function of the auto-closer
0.01~25s
0.001s
3.18 Manual Closing Function
3.18.1 Manual Closing Theory
This relay supports manual closing function (local or remote closing). The manual closing can be
initiated a local input signal (through a binary input or the control panel) or remote closing signal
from a supervision and control system (SAS, SCADA). Three check modes described below can
be selected for the manual closing function.
The logic diagram of the manual closing function is shown as below.
&
ManCls.Inprog
ManCls_Cmd
[25M.En_SynChk]
25M.BI_EnSynChk
25M.Ok_SynChk
[25M.En_DdChk]
25M.BI_EnDdChk
25M.Ok_DdChk
Figure 3.18-1 Logic diagram of the manual closing function
Where:
“ManCls_Cmd” is the manual closing command;
“25M.Ok_SynChk” is the result of the synchronism check of the manual closing function;
“25M.Ok_DdChk” is the result of the dead check of the manual closing function;
“25M.BI_EnSynChk” is the binary input for enabling the synchronism check mode, and it can
be configured through the PCS-Explorer configuration tool auxiliary software;
“25M.BI_EnDdChk” is the binary input for enabling the dead check mode, and it can be
configured through the PCS-Explorer configuration tool auxiliary software;
[25M.En_SynChk] is the logic setting of the synchronism check of the manual closing;
Summary of Contents for PCS-9611
Page 1: ...PCS 9611 Feeder Relay Instruction Manual NR Electric Co Ltd...
Page 2: ......
Page 10: ...1 Introduction PCS 9611 Feeder Relay 1 b Date 2014 04 08...
Page 30: ...2 Technical Data PCS 9611 Feeder Relay 2 14 Date 2014 04 08...
Page 36: ...3 Operation Theory PCS 9611 Feeder Relay 3 f Date 2014 04 08...
Page 108: ...4 Supervision PCS 9611 Feeder Relay 4 b Date 2014 04 08...
Page 116: ...5 Management Function PCS 9611 Feeder Relay 5 b Date 2014 04 08...
Page 120: ...5 Management Function PCS 9611 Feeder Relay 5 4 Date 2014 04 08...
Page 218: ...9 Configurable Function PCS 9611 Feeder Relay 9 b Date 2014 04 08...
Page 232: ...9 Configurable Function PCS 9611 Feeder Relay 9 14 Date 2014 04 08...
Page 262: ...11 Installation PCS 9611 Feeder Relay 11 b Date 2014 04 08...
Page 272: ...12 Commissioning PCS 9611 Feeder Relay 12 b Date 2014 04 08...
Page 292: ...13 Maintenance PCS 9611 Feeder Relay 13 b Date 2014 04 08...
Page 296: ...14 Decommissioning and Disposal PCS 9611 Feeder Relay 14 b Date 2014 04 08...
Page 298: ...14 Decommissioning and Disposal PCS 9611 Feeder Relay 14 2 Date 2014 04 08...
Page 300: ...15 Manual Version History PCS 9611 Feeder Relay 15 2 Date 2014 04 08...